1.13.10 Manual Initialisation
NOTICE
Manual initialisation is not possible on the LCP 2 control
unit. Perform an initialisation with parameter 620
Operation mode.
The following parameters are not set to 0 when initialising
via parameter 620 Operation mode.
parameter 500 Address
parameter 501 Baud rate
parameter 600 Operating hours
parameter 601 Hours run
parameter 602 kWh counter
parameter 603 Number of power-ups
parameter 604 Number of overtemperatures
parameter 605 Number of overvoltages
parameter 615-617 Fault log