EasyManuals Logo

Danfoss VLT 2800 Design Guide

Danfoss VLT 2800
162 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #62 background imageLoading...
Page #62 background image
Parameter 314 Terminal 60, analogue input
current= [2] Feedback (for 4-20 mA transmitters)
Parameter 414 Minimum feedback FB
MIN=Minimum feedback scaling, must be set to
the minimum feedback value
Parameter 415 Maximum feedback,
FBMAX=Maximum feedback scaling, must be set
to the maximum feedback value
Example: Pressure transmitter 0-10 bar: Parameter
414 Minimum feedback FB MIN=0 and Parameter
415 Maximum feedback, FBMAX=10
Parameter 416 Process units=Process units: As
shown in the LCP (example: [4] bar)
Parameter 437 Process PID normal/inverse control=
[0] Normal: Reduce the output frequency when
the feedback signal increases
[1] Inverse: Increase the output frequency when
the feedback signal increases
Parameter 440 Proces PID proportioanl
gain=Proportional gain (P-gain) 0.3-1.0
(experienced value)
Parameter 441 Process PID integration
time=Integration time (I-time) 3-10 s (experienced
value)
Parameter 442 Process PID differentiation time
Differentiation time (D-time) 0-10 s (experienced
value)
Parameter 205 Maximum reference, RefMAX=Max.
reference is to be set equal to Parameter 415
Maximum feedback, FBMAX (example: 10 bar)
Parameter 215 Preset reference 1 (PRESET REF.
1)=Preset reference 1. Set the preset reference to
the wanted min. reference value (example: 5 bar)
(Parameter 205 Maximum reference, RefMAX and
Parameter 215 Preset reference 1 (PRESET REF. 1)
are shown in the process unit chosen in
parameter 416).
The value in brackets [ ] are data values
corresponding to the wanted function. Example:
Parameter 308 Terminal 53, analog input
voltageFeedback signal=[2] Feedback
If the motor is supposed to always run at a
minimum speed, a such can be selected in
Parameter 204 Minimum reference, Ref MIN=output
frequency low limit. (For pump works it is
typically 15-20 Hz).
With the above connections and settings, all
normal pump and fan applications work properly.
In certain cases it might be necessary to optimise
the PID-controllerr (Parameter 440 Proces PID
proportioanl gain, Parameter 441 Process PID
integration time and Parameter 442 Process PID
differentiation time
) beyond the mentioned
experienced values.
Illustration 3.48 Connection for Closed Loop Process Control
Installation Design Guide
60 Danfoss A/S © Rev. May/2014 All rights reserved. MG27E402
33

Table of Contents

Other manuals for Danfoss VLT 2800

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 2800 and is the answer not in the manual?

Danfoss VLT 2800 Specifications

General IconGeneral
Frequency50/60 Hz
EnclosureIP20
Input Voltage200-240V AC
Output Power Range0.37-2.2kW
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overtemperature, Short Circuit
Communication InterfaceRS485
Operating Temperature-10°C to +40°C
Storage Temperature-25°C to +65 °C
Relative Humidity5 - 95% RH, non-condensing
Output Voltage0 - 100% of supply voltage

Related product manuals