Table 69: 380–480 V, Enclosure Sizes A, B, and C
Enclosure
Power [kW (hp)]
Recommended
fuse size
Recommended
maximum fuse
Recommended circuit break-
er Moeller
Maximum trip
level [A]
A2
1.1–3.0 (1.5–4.0)
gG-10
gG-25
PKZM0-25
25
4.0 (5.0)
gG-16
A3
5.5–7.5 (7.5–10.0)
gG-16
gG-32
PKZM0-25
25
A4
1.1–3.0 (1.5–4.0)
gG-10
gG-32
PKZM0-25
25
4.0 (5.0)
gG-16
A5
1.1–3.0 (1.5–4.0)
gG-10
gG-32
PKZM0-25
25
4.0–7.5 (5.0–10.0)
gG-16
B1
11–18 (15–24)
gG-40
gG-80
PKZM4-63
63
B2
22 (30)
gG-50
gG-100
NZMB1-A100
100
30 (40)
gG-63
B3
11–18 (15–24)
gG-40
gG-63
PKZM4-50
50
B4
22 (30)
gG-50
gG-125
NZMB1-A100
100
30 (40)
gG-63
37 (50)
gG-80
C1
37 (50)
gG-80
gG-160
NZMB2-A200
160
45 (60)
gG-100
55 (75)
gG-160
C2
75 (100)
aR-200
aR-250
NZMB2-A250
250
90 (125)
aR-250
C3
45 (60)
gG-100
gG-150
NZMB2-A200
150
55 (75)
gG-160
gG-160
C4
75 (100)
aR-200
aR-250
NZMB2-A250
250
90 (125)
aR-250
Table 70: 525–600 V, Enclosure Sizes A, B, and C
Enclosure
Power [kW (hp)]
Recommended
fuse size
Recommended
maximum fuse
Recommended circuit break-
er Moeller
Maximum trip
level [A]
A2
1.1–4.0 (1.5–5.0)
gG-10
gG-25
PKZM0-25
25
A3
5.5 (7.5)
gG-10
gG-32
PKZM0-25
25
7.5 (10)
gG-16
A5
1.1–5.5 (1.5–7.5)
gG-10
gG-32
PKZM0-25
25
7.5 (10)
gG-16
B1
11 (15)
gG-25
gG-80
PKZM4-63
63
AJ300847815559en-000101 / 130R0337 | 127Danfoss A/S © 2020.09
Electrical Installation
Considerations
VLT® AQUA Drive FC 202
Design Guide