10.12 Eciency
Eciency of the drive (n
VLT
)
The load on the drive has little eect on its eciency. In general, the eciency is the same at the rated motor frequency f
M,N,
even if
the motor supplies 100% of the rated shaft torque or only 75%, for example if there are part loads. This also means that the ecien-
cy of the drive does not change even if other U/f characteristics are selected. However, the U/f characteristics inuence the ecien-
cy of the motor. The eciency declines a little when the switching frequency is set to a value of above 5 kHz. The eciency is also
slightly reduced if the mains voltage is 480 V, or if the motor cable is longer than 30 m (98 ft).
Drive eciency calculation
Calculate the eciency of the drive at dierent speeds and loads based on the graph in Illustration 79. Multiply the factor in this
graph by the specic eciency factor listed in the specication tables in :
e30bd198.10
1
0% 50% 100% 150% 200%
100% Load
75% Load
50% Load
25% Load
1.02
Relative efficiency
0.98
Illustration 79: Typical Eciency Curves
Example: Assume a 160 kW, 380–480/500 V AC drive at 25% load at 50% speed. The graph shows 0.97 - the rated eciency for a
160 kW drive is 0.98. The actual eciency is then: 0.97x0.98=0.95.
The MyDrive
®
ecoSmart
™
tool helps to calculate the eciency, refer to www.ecosmart.danfoss.com.
Eciency of the motor (η
MOTOR
)
The eciency of a motor connected to the drive depends on the magnetizing level. In general, the eciency is as good as with
mains operation. The eciency of the motor depends on the type of motor. In the range of 75–100% of the rated torque, the e-
ciency of the motor is practically constant, both when the drive runs the motor and when it runs directly on mains. In small motors,
the inuence from the U/f characteristic on eciency is marginal. However, in motors from 11 kW (15 hp) and up, the advantages
are signicant. Typically, the switching frequency does not aect the eciency of small motors. Motors from 11 kW (15 hp) and up
have their eciency improved (1–2%) because the shape of the motor current sine-wave is almost perfect at high switching fre-
quency.
Eciency of the system (η
SYSTEM
)
To calculate the system eciency, the eciency of the drive (η
VLT
) is multiplied by the eciency of the motor (η
MOTOR
):
η
SYSTEM
= η
VLT
x η
MOTOR
10.13 Acoustic Noise and Airow
Table 89: Acoustic Noise Ratings
AJ300847815559en-000101 / 130R0337144 | Danfoss A/S © 2020.09
Electrical Installation
Considerations
VLT® AQUA Drive FC 202
Design Guide