Intermittent (60 s overload) (3x525–
550 V) [A]
Continuous (3x551–690 V) [A]
Intermittent (60 s) (3x551–690 V) [A]
Continuous kVA at 550 V [kVA]
Continuous kVA at 690 V [kVA]
Intermittent (60 s overload) (3x525–
550 V) [A]
Continuous (3x551–690 V) [A]
Intermittent (3x551–690 V) [A]
Maximum cable cross–section for mains
and motor [mm
2
(AWG)]
Maximum cable cross–section for brake
and load sharing [mm
2
(AWG)]
Maximum cable cross–section
(3)
for
mains disconnect [mm
2
(AWG)]
185, 150, 120 (350 MCM,
300 MCM, 4/0)
Estimated power loss
(4)
at rated maxi-
mum load [W]
(5)
1
Enclosure sizes for N75K, N90K are D3h for IP20/Chassis, and D5h for IP54/Type 12.
2
High overload=150% or 160% torque for a duration of 60 s. Normal overload=110% torque for a duration of 60 s.
3
The 3 values for the maximum cable cross-section are for single core, exible wire, and exible wire with sleeve, respectively.
4
Applies for dimensioning of drive cooling. If the switching frequency is higher than the default setting, the power losses may increase. LCP and
typical control card power consumptions are included. For more detailed eciency values and part load losses according IEC/EN 61800-9-2 refer to
mydrive ecosmart on
www. danfoss.com. For eciency class see 8.4.1 Environment.
5
Eciency measured at nominal current. For more detailed eciency values and part load losses according IEC/EN 61800-9-2 refer to mydrive ecos-
mart on
www. danfoss.com. For eciency class see 8.4.1 Environment.
6
Measured using 5 m (16 ft) shielded motor cables at rated load and rated frequency. For more detailed eciency values and part load losses ac-
cording IEC/EN 61800-9-2 refer to mydrive ecosmart on
www. danfoss.com. For eciency class see 8.4.1 Environment.
8.2 Mains Supply
Maximum imbalance temporary between mains phases
3.0% of rated supply voltage
≥0.9 nominal at rated load
AJ300847815559en-000101 / 130R0337 | 89Danfoss A/S © 2020.09
Specications
VLT® AQUA Drive FC 202
Design Guide