Danfoss VLT AQUA FC 202 Design Guide

Danfoss VLT AQUA FC 202
218 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #89 background imageLoading...
Page #89 background image
Type designation
P37K
P45K
P55K
P75K
(1)
P90K/N90K
(1)
Intermittent (60 s overload) (3x525–
550 V) [A]
54
47.3
64.5
59.4
81
71.5
97.5
95.7
130.5
115.5
Continuous (3x551–690 V) [A]
34
41
41
52
52
62
62
83
83
100
Intermittent (60 s) (3x551–690 V) [A]
51
45.1
61.5
57.2
78
68.2
93
91.3
124.5
110
Continuous kVA at 550 V [kVA]
34.3
41
41
51.4
51.4
61.9
61.9
82.9
82.9
100
Continuous kVA at 690 V [kVA]
40.6
49
49
62.1
62.1
74.1
74.1
99.2
99.2
119.5
Maximum input current
Continuous 550 V [A]
36
49
49
59
59
71
71
87
87
99
Intermittent (60 s overload) (3x525–
550 V) [A]
54
53.9
72
64.9
87
78.1
105
95.7
129
108.9
Continuous (3x551–690 V) [A]
36
48
48
58
58
70
70
86
Intermittent (3x551–690 V) [A]
54
52.8
72
63.8
87
77
105
94.6
Additional specications
Maximum cable cross–section for mains
and motor [mm
2
(AWG)]
150 (300 MCM)
Maximum cable cross–section for brake
and load sharing [mm
2
(AWG)]
95 (3/0)
Maximum cable cross–section
(3)
for
mains disconnect [mm
2
(AWG)]
95 (3/0)
185, 150, 120 (350 MCM,
300 MCM, 4/0)
Estimated power loss
(4)
at rated maxi-
mum load [W]
(5)
600
740
740
900
900
1100
1100
1500
1500
1800
Eciency
(6)
0.98
1
Enclosure sizes for N75K, N90K are D3h for IP20/Chassis, and D5h for IP54/Type 12.
2
High overload=150% or 160% torque for a duration of 60 s. Normal overload=110% torque for a duration of 60 s.
3
The 3 values for the maximum cable cross-section are for single core, exible wire, and exible wire with sleeve, respectively.
4
Applies for dimensioning of drive cooling. If the switching frequency is higher than the default setting, the power losses may increase. LCP and
typical control card power consumptions are included. For more detailed eciency values and part load losses according IEC/EN 61800-9-2 refer to
mydrive ecosmart on
www. danfoss.com. For eciency class see 8.4.1 Environment.
5
Eciency measured at nominal current. For more detailed eciency values and part load losses according IEC/EN 61800-9-2 refer to mydrive ecos-
mart on
www. danfoss.com. For eciency class see 8.4.1 Environment.
6
Measured using 5 m (16 ft) shielded motor cables at rated load and rated frequency. For more detailed eciency values and part load losses ac-
cording IEC/EN 61800-9-2 refer to mydrive ecosmart on
www. danfoss.com. For eciency class see 8.4.1 Environment.
8.2 Mains Supply
Supply terminals
L1, L2, L3
Supply voltage
(1)(2)
200–240 V ±10%
Supply voltage
(1)(2)
380–480 V/500–600 V ±10%
Supply voltage
(1)(2)
525–600 V ±10%
Supply frequency
(3)
47.5–63 Hz
Maximum imbalance temporary between mains phases
3.0% of rated supply voltage
True power factor (λ)
≥0.9 nominal at rated load
AJ300847815559en-000101 / 130R0337 | 89Danfoss A/S © 2020.09
Specications
VLT® AQUA Drive FC 202
Design Guide

Table of Contents

Other manuals for Danfoss VLT AQUA FC 202

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AQUA FC 202 and is the answer not in the manual?

Danfoss VLT AQUA FC 202 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AQUA FC 202
CategoryDC Drives
LanguageEnglish

Related product manuals