Type designation
P3K0
P4K0
P5K5
P7K5
Eciency
(5)
0.97
1
High overload=150% or 160% torque for a duration of 60 s. Normal overload=110% torque for a duration of 60 s.
2
The 3 values for the maximum cable cross-section are for single core, exible wire, and exible wire with sleeve, respectively.
3
Applies for dimensioning of drive cooling. If the switching frequency is higher than the default setting, the power losses may increase. LCP and
typical control card power consumptions are included. For more detailed eciency values and part load losses according IEC/EN 61800-9-2 refer to
mydrive ecosmart on
www. danfoss.com. For eciency class see 8.4.1 Environment.
4
Eciency measured at nominal current. For more detailed eciency values and part load losses according IEC/EN 61800-9-2 refer to mydrive ecos-
mart on www. danfoss.com. For eciency class see 8.4.1 Environment.
5
Measured using 5 m (16 ft) shielded motor cables at rated load and rated frequency. For more detailed eciency values and part load losses ac-
cording IEC/EN 61800-9-2 refer to mydrive ecosmart on
www. danfoss.com. For eciency class see 8.4.1 Environment.
Table 37: Mains supply 3x525–600 V AC, P11K–P37K
Type designation
P11K
P15K
P18K
P22K
P30K
P37K
High/normal overload
(1)
HO
NO
HO
NO
HO
NO
HO
NO
HO
NO
HO
NO
Typical shaft output [kW]
7.5
11
11
15
15
18.5
18.5
22
22
30
30
37
Typical shaft output [hp]
10
15
15
20
20
25
25
30
30
40
40
50
Protection rating IP20/Chassis
B3
B3
B3
B4
B4
B4
Protection rating IP21/Type 1
Protection rating IP55/Type 12
Protection rating IP66/NEMA 4X
B1
B1
B1
B2
B2
C1
Output current
Continuous (3x525–550 V) [A]
11.5
19
19
23
23
28
28
36
36
43
43
54
Intermittent (3x525– 550 V) [A]
18.4
21
30
25
37
31
45
40
58
47
65
59
Continuous (3x551–600 V) [A]
11
18
18
22
22
27
27
34
34
41
41
52
Intermittent (3x551– 600 V) [A]
17.6
20
29
24
35
30
43
37
54
45
62
57
Continuous kVA at 550 V [kVA]
11
18.1
18.1
21.9
21.9
26.7
26.7
34.3
34.3
41
41
51.4
Continuous kVA at 575 V [kVA]
11
17.9
17.9
21.9
21.9
26.9
26.9
33.9
33.9
40.8
40.8
51.8
Maximum input current
Continuous at 550 V [A]
10.4
17.2
17.2
20.9
20.9
25.4
25.4
32.7
32.7
39
39
49
Intermittent at 550 V [A]
16.6
19
28
23
33
28
41
36
52
43
59
54
Continuous at 575 V [A]
9.8
16
16
20
20
24
24
31
31
37
37
47
Intermittent at 575 V [A]
15.5
17.6
26
22
32
27
39
34
50
41
53
52
Maximum pre-fuses [A]
40
40
50
60
80
100
Additional specications
Protection rating IP20, maximum cable
crosssection
(2)
for mains, brake, motor,
and load sharing [mm
2
(AWG)]
10, 10, – (8, 8, –)
35, –, –
AJ300847815559en-000101 / 130R033784 | Danfoss A/S © 2020.09
Specications
VLT® AQUA Drive FC 202
Design Guide

Table of Contents

Other manuals for Danfoss VLT AQUA FC 202

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AQUA FC 202 and is the answer not in the manual?

Danfoss VLT AQUA FC 202 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AQUA FC 202
CategoryDC Drives
LanguageEnglish

Related product manuals