Power [kW
(hp)]
SIBA Type RK1
Littelfuse
Type RK1
Ferraz-
Shawmut
Type CC
Ferraz- Shaw-
mut Type RK1
Bussmann
Type JFHR2
Littel-
fuse
JFHR2
Ferraz-
Shawmut
JFHR2
(1)
Ferraz-
Shawmut
J
90 (125)
2028220-250
KLN-R-250
A6K-250-R
FWH-250
L50-
S-250
A50-P-250
HSJ-250
1
Ferraz-Shawmut A50QS fuses may substitute A50P fuses.
Table 80: Recommended Maximum Fuse, 525–600 V, Enclosure Sizes A, B, and C
Power [kW (hp)
Bussmann Type
RK1
Bussmann
Type J
Bussmann
Type T
Bussmann
Type CC
Bussmann
Type CC
Bussmann
Type CC
0.75–1.1 (1–1.5)
KTS-R-5
JKS-5
JJS-6
FNQ-R-5
KTK-R-5
LP-CC-5
1.5–2.2 (2.0– 3.0)
KTS-R-10
JKS-10
JJS-10
FNQ-R-10
KTK-R-10
LP-CC-10
3.0 (4.0)
KTS-R15
JKS-15
JJS-15
FNQ-R-15
KTK-R-15
LP-CC-15
4.0 (5.0)
KTS-R20
JKS-20
JJS-20
FNQ-R-20
KTK-R-20
LP-CC-20
5.5 (7.5)
KTS-R-25
JKS-25
JJS-25
FNQ-R-25
KTK-R-25
LP-CC-25
7.5 (10.0)
KTS-R-30
JKS-30
JJS-30
FNQ-R-30
KTK-R-30
LP-CC-30
11–15 (15–20)
KTS-R-35
JKS-35
JJS-35
18 (24)
KTS-R-45
JKS-45
JJS-45
22 (30)
KTS-R-50
JKS-50
JJS-50
30 (40)
KTS-R-60
JKS-60
JJS-60
37 (50)
KTS-R-80
JKS-80
JJS-80
45 (60)
KTS-R-100
JKS-100
JJS-100
55 (75)
KTS-R-125
JKS-125
JJS-125
75 (100)
KTS-R-150
JKS-150
JJS-150
90 (125)
KTS-R-175
JKS-175
JJS-175
Table 81: Recommended Maximum Fuse, 525–600 V, Enclosure Sizes A, B, and C
Power [kW (hp)
SIBA Type RK1
Littelfuse Type RK1
Ferraz Shawmut Type RK1
Ferraz Shawmut J
0.75–1.1 (1–1.5)
5017906-005
KLS-R-005
A6K-5-R
HSJ-6
1.5–2.2 (2.0– 3.0)
5017906-010
KLS-R-010
A6K-10-R
HSJ-10
3.0 (4.0)
5017906-016
KLS-R-015
A6K-15-R
HSJ-15
4.0 (5.0)
5017906-020
KLS-R-020
A6K-20-R
HSJ-20
5.5 (7.5)
5017906-025
KLS-R-025
A6K-25-R
HSJ-25
7.5 (10.0)
5017906-030
KLS-R-030
A6K-30-R
HSJ-30
11–15 (15–20)
5014006-040
KLS-R-035
A6K-35-R
HSJ-35
18 (24)
5014006-050
KLS-R-045
A6K-45-R
HSJ-45
22 (30)
5014006-050
KLS-R-050
A6K-50-R
HSJ-50
AJ300847815559en-000101 / 130R0337 | 133Danfoss A/S © 2020.09
Electrical Installation
Considerations
VLT® AQUA Drive FC 202
Design Guide

Table of Contents

Other manuals for Danfoss VLT AQUA FC 202

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AQUA FC 202 and is the answer not in the manual?

Danfoss VLT AQUA FC 202 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AQUA FC 202
CategoryDC Drives
LanguageEnglish

Related product manuals