Type designation
P1K1
P1K5
P2K2
P3K0
P3K7
Eciency
(6)
0.96
1
High overload=150% or 160% torque for a duration of 60 s. Normal overload=110% torque for a duration of 60 s.
2
Enclosure sizes A2+A3 can be converted to IP21 using a conversion kit. See also chapters Mechanical mounting and IP21/Type 1 Enclosure kit in the
design guide.
3
The 3 values for the maximum cable cross-section are for single core, exible wire, and exible wire with sleeve, respectively.
4
Applies for dimensioning of drive cooling. If the switching frequency is higher than the default setting, the power losses may increase. LCP and
typical control card power consumptions are included. For more detailed eciency values and part load losses according IEC/EN 61800-9-2 refer to
mydrive ecosmart on
www. danfoss.com. For eciency class see 8.4.1 Environment.
5
Eciency measured at nominal current. For more detailed eciency values and part load losses according IEC/EN 61800-9-2 refer to mydrive ecos-
mart on
www. danfoss.com. For eciency class see 8.4.1 Environment.
6
Measured using 5 m (16 ft) shielded motor cables at rated load and rated frequency. For more detailed eciency values and part load losses ac-
cording IEC/EN 61800-9-2 refer to mydrive ecosmart on
www. danfoss.com. For eciency class see 8.4.1 Environment.
Table 28: Mains Supply 3x200–240 V AC, P5K5–P15K
Type designation
P5K5
P7K5
P11K
P15K
High/normal overload
(1)
HO
NO
HO
NO
HO
NO
HO
NO
Typical shaft output [kW]
3.7
5.5
5.5
7.5
7.5
11
11
15
Typical shaft output at 208 V [hp]
5.0
7.5
7.5
10
10
15
15
20
IP20/Chassis
(2)
B3
B3
B3
B4
Protection rating IP21/Type 1
Protection rating IP55/Type 12
Protection rating IP66/NEMA 4X
B1
B1
B1
B2
Output current
Continuous (3x200–240 V) [A]
16.7
24.2
24.2
30.8
30.8
46.2
46.2
59.4
Intermittent (3x200–240 V) [A]
26.7
26.6
38.7
33.9
49.3
50.8
73.9
65.3
Continuous kVA at 208 V [kVA]
6.0
8.7
8.7
11.1
11.1
16.6
16.6
21.4
Maximum input current
Continuous (3x200–240 V) [A]
15
22
22
28
28
42
42
54
Intermittent (3x200–240 V) [A]
24
24.2
35.2
30.8
44.8
46.2
67.2
59.4
Maximum pre-fuses [A]
63
63
63
80
Additional specications
IP20 maximum cable cross-section
(3)
for mains,
brake, motor, and load sharing [mm
2
(AWG)]
10, 10, – (8, 8, –)
10, 10, – (8, 8, –)
10, 10, – (8, 8, –)
35, –, – (2, –, –)
Protection rating IP21 maximum cable cross-sec-
tion
(3)
for mains, brake, and load sharing [mm
2
(AWG)]
16, 10, 16 (6, 8, 6)
16, 10, 16 (6, 8, 6)
16, 10, 16 (6, 8, 6)
35, –, – (2, –, –)
Protection rating IP21 maximum cable cross-sec-
tion
(3)
for motor [mm
2
(AWG)]
10, 10, – (8, 8, –)
10, 10, – (8, 8, –)
10, 10, – (8, 8, –)
35, 25, 25 (2, 4, 4)
Maximum cable cross-section
(3)
for mains discon-
nect [mm
2
(AWG)]
16, 10, 10 (6, 8, 8)
35 (2)
AJ300847815559en-000101 / 130R033774 | Danfoss A/S © 2020.09
Specications
VLT® AQUA Drive FC 202
Design Guide

Table of Contents

Other manuals for Danfoss VLT AQUA FC 202

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AQUA FC 202 and is the answer not in the manual?

Danfoss VLT AQUA FC 202 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AQUA FC 202
CategoryDC Drives
LanguageEnglish

Related product manuals