EasyManua.ls Logo

Danfoss VLT AutomationDrive FC 301

Danfoss VLT AutomationDrive FC 301
92 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Table 24: Motor Thermistor
Parameters
e30bb686.13
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
+10
V
A IN
A IN
COM
A OUT
COM
12
13
18
19
20
27
29
32
33
50
53
54
55
42
39
A53
U - I
D IN
37
Drive
Function
Setting
Parameter 1-90 Motor Thermal Protection
[2] Thermistor trip
Parameter 1-93 Thermistor Source
[1] Analog input 53
* = Default value
If only a warning is required, set parameter 1-90 Motor Thermal Protection to [1] Thermistor warn-
ing.
D IN 37 is an option.
6.1.11 Wiring for Regen
Table 25: Regen
Parameters
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN
+10
V
A IN
A IN
COM
A OUT
COM
12
13
18
19
20
27
29
32
33
37
50
53
54
55
42
39
e30bd667.11
Drive
Function
Setting
Parameter 1-90 Motor Thermal Protection
100%*
* = Default value
AQ267037727118en-000101 / 130R0300 | 37Danfoss A/S © 2021.01
Basic I/O Configuration
VLT® AutomationDrive FC 301/FC 302
Operating Guide

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 301

Related product manuals