8.11.4.2 Bit 01, Drive Ready
Bit 01=0: The drive is not ready.
Bit 01=1: The drive is ready for operation, but the coasting command is active via the digital inputs or via serial communication.
8.11.4.3 Bit 02, Coast Stop
Bit 02=0: The drive releases the motor.
Bit 02=1: The drive starts the motor with a start command.
8.11.4.4 Bit 03, No Error/Trip
Bit 03=0: The drive is not in fault mode.
Bit 03=1: The drive trips. To re-establish operation, press [Reset].
8.11.4.5 Bit 04, No Error/Error (No Trip)
Bit 04=0: The drive is not in fault mode.
Bit 04=1: The drive shows an error but does not trip.
8.11.4.6 Bit 05, Not Used
Bit 05 is not used in the status word.
8.11.4.7 Bit 06, No Error/Triplock
Bit 06=0: The drive is not in fault mode.
Bit 06=1: The drive is tripped and locked.
8.11.4.8 Bit 07, No Warning/Warning
Bit 07=0: There are no warnings.
Bit 07=1: A warning has occurred.
8.11.4.9 Bit 08, Speed ≠ Reference/Speed=Reference
Bit 08=0: The motor runs, but the present speed is different from the preset speed reference. It might happen when the speed
ramps up/down during start/stop.
Bit 08=1: The motor speed matches the preset speed reference.
8.11.4.10 Bit 09, Local Operation/Bus Control
Bit 09=0: [Off/Reset] is activated on the control unit or [2] Local in parameter 3-13 Reference Site is selected. It is not possible to con-
trol the drive via serial communication.
Bit 09=1: It is possible to control the drive via the fieldbus/serial communication.
8.11.4.11 Bit 10, Out of Frequency Limit
Bit 10=0: The output frequency has reached the value in parameter 4-12 Motor Speed Low Limit [Hz] or parameter 4-14 Motor Speed
High Limit [Hz].
Bit 10=1: The output frequency is within the defined limits.
8.11.4.12 Bit 11, No Operation/In Operation
Bit 11=0: The motor is not running.
Bit 11=1: The drive has a start signal or the output frequency is greater than 0 Hz.
8.11.4.13 Bit 12, Drive OK/Stopped, Auto Start
Bit 12=0: There is no temporary overtemperature on the drive.
Bit 12=1: The drive stops because of overtemperature but the unit does not trip and resumes operation once the overtemperature
normalizes.
8.11.4.14 Bit 13, Voltage OK/Limit Exceeded
Bit 13=0: There are no voltage warnings.
AJ363928382091en-000101 / 130R0983 | 129Danfoss A/S © 2021.04
RS485 Installation and Set-up
VLT® Flow Drive FC 111
Design Guide

Table of Contents

Other manuals for Danfoss VLT Flow Drive FC 111

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT Flow Drive FC 111 and is the answer not in the manual?

Danfoss VLT Flow Drive FC 111 Specifications

General IconGeneral
BrandDanfoss
ModelVLT Flow Drive FC 111
CategoryDC Drives
LanguageEnglish

Related product manuals