Mains supply 6x525–690 V AC
FC 302 P630 P710 P800
High/Normal Load
A)
HO/NO
HO NO HO NO HO NO
Typical shaft output at 550 V [kW] 500 560 560 670 670 750
Typical shaft output at 575 V [hp] 650 750 750 950 950 1050
Typical shaft output at 690 V [kW] 630 710 710 800 800 900
Enclosure protection rating IP21, IP54
without/with options cabinet
F10/F11 F10/F11 F10/F11
Output current
Continuous
(at 550 V) [A]
659 763 763 889 889 988
Intermittent (60 s overload)
(at 550 V) [A]
989 839 1145 978 1334 1087
Continuous
(at 575/690 V) [A]
630 730 730 850 850 945
Intermittent (60 s overload)
(at 575/690 V) [A]
945 803 1095 935 1275 1040
Continuous kVA
(at 550 V) [kVA]
628 727 727 847 847 941
Continuous kVA
(at 575 V) [kVA]
627 727 727 847 847 941
Continuous kVA
(at 690 V) [kVA]
753 872 872 1016 1016 1129
Maximum input current
Continuous
(at 550 V) [A]
642 743 743 866 866 962
Continuous
(at 575 V) [A]
613 711 711 828 828 920
Continuous
(at 690 V) [A]
613 711 711 828 828 920
Maximum cable size, motor
[mm
2
(AWG
2)
)]
8x150
(8x300 MCM)
Maximum cable size, mains
[mm
2
(AWG
2)
)]
6x120
(6x250 MCM)
Maximum cable size, brake
[mm
2
(AWG
2)
)
4x185
(4x350 MCM)
Maximum external mains fuses [A]
1)
900
Estimated power loss
at 600 V [W]
4)
9201 10771 10416 12272 12260 13835
Estimated power loss
at 690 V [W]
4)
9674 11315 10965 12903 12890 14533
F3/F4 maximum added losses CB or
disconnect & contactor
342 427 419 532 519 615
Maximum panel options losses [W] 400
Weight,
enclosure protection rating IP21, IP54
[kg (lb)]
1004/1299 (2213/2864) 1004/1299 (2213/2864) 1004/1299 (2213/2864)
Weight, rectier module [kg (lb)] 102 (225) 102 (225) 102 (225)
Weight, inverter module [kg (lb)] 102 (225) 102 (225) 136 (300)
Eciency
4)
0.98
Output frequency 0–590 Hz
Heat sink overtemperature trip
85 °C (185 °F)
Power card ambient trip
75 °C (167 °F)
A)
High overload = 150% torque during 60 s, Normal overload = 110% torque during 60 s
Table 5.4 Mains Supply 6x525–690 V AC
General Specications Operating Instructions
MG34Q402 Danfoss A/S © 04/2016 All rights reserved. 79
5 5

Table of Contents

Other manuals for Danfoss VLT series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT series and is the answer not in the manual?

Danfoss VLT series Specifications

General IconGeneral
SeriesVLT
CategoryDC Drives
Output Voltage0-100% of input voltage
Protection FeaturesOvervoltage, Undervoltage, Overcurrent, Overtemperature, Short Circuit, Ground Fault
Communication InterfacesProfibus, CANopen
Enclosure RatingIP20, IP21, IP55, IP66
Cooling MethodForced Air Cooling, Convection Cooling
Control ModeSensorless Vector, Closed Loop Vector
Ambient Temperature-10°C to +50°C (14°F to 122°F)