4 Rinse the central heating installation with at least 3x
the volume of the central heating installation.
4 Flush the DHW pipes with at least 20 times the volume
of the pipes.
For an optimum functioning of the boiler, the water of the installation
must comply with following characteristics:
Output ≤ 70 kW
Acidity (pH)
7.5 - 9
Conductivity at 25°C µS/cm 10 to 500
Chlorides mg/l < 50
Other components mg/l < 1
Hardness of the water of the installation °f 7- 15
°dH 4- 8.5
If a water treatment is necessary, De Dietrich
Thermique recommends the following manufacturers:
4 Cillit
4 Climalife
4 Fernox
4 Permo
4 Sentinel
4.10.2. Filling the system
CAUTION
Do not use glycol.
The heat pump components are not designed to be used
with glycol.
The use of glycol in the heating circuit invalidates the
warranty.
4 Fill the installation until a pressure of 1.5 to 2 bars is reached.
Water pressure display: See chapter: ¼ "Reading out
measured values", page 88.
4 Check for any water leaks.
4 Completely vent the indoor module and the installation for
optimum functioning.
AWHP MIT-IN iSystem
4. Installation
24/09/2012 - 300027606-001-01
40

Table of Contents

Other manuals for DeDietrich AWHP MIT-IN iSystem

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the DeDietrich AWHP MIT-IN iSystem and is the answer not in the manual?

DeDietrich AWHP MIT-IN iSystem Specifications

General IconGeneral
BrandDeDietrich
ModelAWHP MIT-IN iSystem
CategoryHeat Pump
LanguageEnglish

Related product manuals