6.1.8 Profibus DP (option H3)
Connection with 2-wire screened cable (recommended):
Multi-line
DATA + (B)
29 30 31
COM
DATA - (A)
Multi-line
DATA + (B)
29 30 31
COM
DATA - (A)
Multi-line
DATA + (B)
29 30 31
COM
DATA - (A)
DATA - (A)
PLC or other device
COM
DATA + (B)
Connect shield to ground at one end only. Shield ends must be insulated with tape or insula-
tion tubing.
Use shielded twisted cable.
ML-2 installation instructions 4189340582
UK
Wirings
DEIF A/S Page 47 of 64