50
Cod.: 240.010.0042
DLS / DLS-C Series
4.3 Checking the Box Contents
The DLS box must contain the following parts:
DLS hybrid inverter.
Top and bottom bracket for wall mounting.
Support for wall mounting.
Instruction manual - Operation, installation, maintenance.
Quick connectors and related contacts for PV strings wiring and connection.
Wi-Fi dongle for connection to a local wireless network.
4.4 Positioning the DLS
With reference to Figure 01, the installation position of the DLS must meet the following conditions:
The DLS must be installed indoors in a room with relative humidity ranging from 5% to 95% without
condensation.
The DLS optimal operation is ensured if the maximum ambient temperature of 40°C is not excee-
ded. Should the temperature become too high, the automatic power derating will trip to prevent the
system from overheating.
Do not install the DLS in a position directly exposed to the sun.
Install the DLS as close as possible to the meter panel.
Install the DLS in such a way as to Ensure easy access to the controls and to the connections
Install the DLS in such a way as to have the LCD display at eye height.
Install the DLS and the power lines in such a way as to prevent access to pets (rodents in Particu-
lar).
The DLS, in some specic conditions, can produce a slight buzzing noise during its operation. This
noise is normal and does not affect its performance but can be annoying if the unit is mounted
onto a wall of an inhabited area, onto a wall adjacent to an inhabited area or onto certain type of
materials (such as thin wooden panels or metal plates).
The position must not be accessible to children.
The wall must be vertical, with a maximum tilt of ±5°.
The surface where the DLS will be installed must withstand its weight (25kg).
The DLS must be installed leaving a 500mm clearance where the bottom of the unit is located to
Ensure easy cabling and connection. There are no restrictions for the top of the unit as the venti-
lation system does not require vertical outlets.
In the case of multiple installation of several DLS, a side clearance of 500 mm between the units
must be provided.
The DLS system must be used at a maximum altitude above sea level of 3000m (9750 feet). For
altitudes above 2000m, due to the rarefaction of the air, specic conditions may occur which must
be considered when choosing the place of installation. All installations at altitudes above 2000m
must be assessed case by case considering the following critical issues:
- less efcient cooling,
- decrease in the dielectric strength of the air and, in the presence of high voltages, the creation
of electric arcs,
- presence of cosmic radiation that can affect the correct functioning of the electronic components.
• Do not mount the DLS on or under ammable building materials.
• Do not install the DLS in areas where highly ammable substances are present.
• Do not install the DLS in areas subject to explosion hazard.