DLS / DLS-C Series
85
Cod.: 240.010.0042
change at any time and without notice.
3. "CH/DISCH PAR." - The page allows to set the maximum charge and discharge current. The set va-
lue represents the maximum value allowed by the inverter. The charge/discharge set-point is anyway
dened by the bat-tery BMS which is based on the state of charge and the temperature of the battery
itself. The set-tings are accessible only in the INSTALLER mode which require a password to be log-
ged in (see the "LOGIN menu" section).
4. "BATT. MAINT. SETUP" - The page allows to set the battery maintenance parameters. The settings
are accessible only in the INSTALLER mode which require a password to be logged in (see the "LO-
GIN menu" section).
PARAMETER VALUE DESCRIPTION
Battery Maint. Sel. ON/OFF BATTERY MAINTENANCE enable (Default = ON).
Giorni per Manut. 0 -20
Number of days after which forced maintenance from the grid is activated if
the maintenance charge carried out only with PV energy was not sufcient.
(Default = 7)
Max Iac per Manut. 0 - Inom Max AC current from grid (Default = 4.3A)
Pmax grid counter
Fun.
--
Access to the settings for the dynamic charge power control function which
prevents the home plant from exceeding the maximum power limit allowed
by the grid and prevents disconnections by the grid operator.
Pmax grid counter sel. ON/OFF PMAX GRID COUNTER enable (Default = OFF)
Pmax grid counter 0 - 99999 Maximum power from the grid allowed for the home plant (Default = 3000W)