Chapter 3 Product Specifications
3-3
3_
3.2 Ethernet/IP Specifications
3.2.1 AHCPU5x1-EN/ AHCPU560-EN2
Item
Specification
General
Category
Scanner / Adapter
Topology
Star
CIP Network
I/O Connection
Max. Number of the CIP
Connections
AHCPU501-EN: 32 (Clients + Servers)
AHCPU511-EN: 64 (Clients + Servers)
AHCPU521-EN: 128 (Clients + Servers)
AHCPU531-EN: 256 (Clients + Servers)
AHCPU560-EN2: 256 (Clients + Servers)
Max. Number of the TCP
Connections
AHCPU501-EN: 16 (Clients + Servers)
AHCPU511-EN: 32 (Clients + Servers)
AHCPU521-EN: 64 (Clients + Servers)
AHCPU531-EN: 128 (Clients + Servers)
AHCPU560-EN2: 128 (Clients + Servers)
Requested Packet Interval (RPI)
1 ms~1000 ms
Max. Transmission Speed
10000 pps
Max. Data Length
500 bytes
CIP Network
Explicit Message
Class 3 (Connected Type)
Total 32 (Clients + Servers), including the clients +
servers from the UCMM type (for V2.1 or later version)
UCMM (Non-Connected Type)
Total 32 (Clients + Servers) , including the clients +
servers from the Class 3 (for V2.1 or later version)
CIP Objects
Identity Object (16#01)
Message Router Object (16#02)
Assembly Object (16#04)
Connection Manager Object (16#06)
Port Object (16#F4)
TCP/IP Interface Object (16#F5)
Ethernet Link Object (16#F6)
CIP Network
Produced Tag
Max. Number of the CIP
Connections
32 (Clients + Servers) (for V2.1 or later version)
Max. Data Length
500 bytes
Requested Packet Interval (RPI)
1 ms~1000 ms
CIP Network
Consumed Tag
Max. Number of the CIP
Connections
32 (Clients + Servers) (for V2.1 or later version)
Max. Data Length
500 bytes
Requested Packet Interval (RPI) 1 ms~1000ms