Chapter 8 Parameters ASDA-A2
8-20 Revision February, 2017
P0-08
TSON Power On Time
Address: 0010H
0011H
Operational
Interface
Panel / Software Communication
Related Section-
Default
0
Control
Mode
-
Unit
Hour
Range
0 ~ 65535
Data Size
16-bit
Format
Decimal
Settings
It shows the total startup time of the servo drive.
P0-09
CM1 Status Monitor Register 1
Address: 0012H
0013H
Operational
Interface
Panel / Software Communication
Related Section:
4.3.5
Default
-
Control
Mode
ALL
Unit
-
Range
-
Data Size
32-bit
Format
Decimal
Settings
The setting value which is set by P0-17 should be monitored via P0-09.
(Please refer to Chapter 7.2.1, Description of Monitoring Variable for
the setting value.)
For example, if P0-17 is set to 3, when accessing P0-09, it obtains the
total feedback pulse number of motor encoder. For MODBUS
communication, two 16-bit data, 0012H and 0013H will be read as a
32-bit data; (0013H : 0012H) = (Hi-wordLow-word).
Set P0-02 to 23, the panel displays VAR-1 first, and then shows the
content of P0-09.