VFD-V Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
8-22
Control Mode
Parameters Functions Settings
Factory
Setting
VF VG SV SG T TG
a
06-09
Over-Torque
Detection
Selection 2 (OL3)
0: Disable
1: over-torque detection during
constant speed operation,
continue to operate after
detection
2: over-torque detection during
constant speed operation,
stop operation after detection.
3: over-torque detection during
operation, continue operation
after detection.
4: over-torque detection during
operation, stop operation after
detection.
0
{ { { { { {
a
06-10
Over-Torque
Detection Level 2
(OL3)
10~250% 150
{ { { { { {
a
06-11
Over-Torque
Detection Time 2
(OL3)
0.0~60.0 Sec 0.1
{ { { { { {
a
06-12 Over-Torque limit
0250%
150
° ° { { { {
a
06-13
Electronic
Thermal Relay
Selection (I
2
t)
0: Inverter/vector motor
1: Standard motor
2: Electronic thermal relay
function disabled
2
{ { { { { {
a
06-14
Electronic
Thermal Relay
Time (I
2
t)
30~600 Sec 60
{ { { { { {
a
06-15
Heat Sink
Over-Heat (oH)
Warning
0.0~110.0
85.0
{ { { { { {
a
06-16 Op stall low limit 0~250% 120
{ { { { { {
0: no fault
{ { { { { {
1: oc (over-current)
{ { { { { {
2: ov (over-voltage)
{ { { { { {
3: oH1 (IGBT overheat)
{ { { { { {
06-17
Most Recent Fault
Record
4: oL (drive overload)
0
{ { { { { {