- 101 -
Secondary Earth Nominal Current
This field enables the declaration of the secondary
earth nominal current and earth protection range. The
options available for the field are listed below.
6
Option
Earth Protection Type
Range
I
en
T1-1A
T1 (Type 1)
(0.1 - 40) I
en
1 A
T1-5A
T1 (Type 1)
(0.1 - 40) I
en
5 A
T2-1A
T2 (Type 2)
(0.02 - 5) I
en
1 A
T2-5A
T2 (Type 2)
(0.02 - 5) I
en
5 A
WARNING!
Setting current transformers characteristics on the
Current Transformers Menu does not provide the
correct operation of CPM 310 G by itself; but also, the
dip-switch settings must also be done! Incomplete and
inappropriate settings on the menus and dip-switches
may result in secondary protection, selectivity and
supply continuity failures, performance drops and
misinterpretations!
Please see the
Dip-Switch Settings
section for detailed
information on the secondary signal processing
principles of CPM 310 G, at p.47 of this manual. □
6
Please read the warnings on this page!