1592022750 Quick reference guide IC 200CX Rel. 1.1 25/05/2009
CO 11
Part - winding start-up time.
To change the time delay between the activation of two contactors of
the two compressor circuits
0 100 Sec/10
0.1 sec
CO 12
By-pass gas valve start-up time / automatic start-unloading valve
(capacity step control)
0 250 sec
Rotating – Balancing – Compressors Thermoregulation
CO 13
Compressor rotation (See compressor rotation)
0 = Sequential
1 = Compressors rotation based on time running hours
2 = Compressors rotation based on number of starts-up
0 2
CO 14
Circuit balancing (See Circuit balancing)
0= Circuit saturation
1= Circuit balancing
0 1
Evaporator water pump / supply fan
CO 15
Operative mode of the evaporator pump / supply fan
0= Not enabled (evaporator pump or supply fan).
1= ON/OFF: continuous operation type 1
When the unit is running in Chiller or Heat Pump the pump or the
supply fan is running. In std-by or remote OFF mode, the pump is
OFF.
2= ON/OFF: on if called by compressor
When a compressor is running, the pump or the supply fan is running.
3= ON/OFF: continuous operation type 2
When the unit is running in Chiller or Heat Pump or in STD-By or in
OFF, the pump or the supply fan is running.
4= Modulation: continuous operation type 1
When the unit is running in Chiller or Heat Pump the pump or the
supply fan is running. In std-by or remote OFF mode, the pump is
OFF.
5= Modulation: on if called by compressor
When a compressor is running, the pump or the supply fan is running.
6= Modulation: continuous operation type 2
When the unit is running in Chiller or Heat Pump or in STD-By or in
OFF, the pump or the supply fan is running.
0 6
CO 16
ON compressor delay after water pump / supply fan start-up 1 250 10 sec
10 sec
CO 17
OFF delay evaporator water pump / supply fan after compressor
switching OFF. This delay is also active when the unit is turned in
stand-by
0 250 Min
CO 18
Number of running hours for evaporator pump rotation 0 999 10Hr 10Hr
CO 19
Contemporary working time of the pumps during rotation 0 250 Sec
Condenser water pump

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the dixell IC200CX Series and is the answer not in the manual?

dixell IC200CX Series Specifications

General IconGeneral
Branddixell
ModelIC200CX Series
CategoryTemperature Controller
LanguageEnglish

Related product manuals