Part - winding start-up time.
To change the time delay between the activation of two contactors of
the two compressor circuits
0 100 Sec/10
Compressor rotation (See compressor rotation)
0 = Sequential
1 = Compressors rotation based on time running hours
2 = Compressors rotation based on number of starts-up
0 2
CO 14
Operative mode of the evaporator pump / supply fan
0= Not enabled (evaporator pump or supply fan).
1= ON/OFF: continuous operation type 1
When the unit is running in Chiller or Heat Pump the pump or the
supply fan is running. In std-by or remote OFF mode, the pump is
OFF.
2= ON/OFF: on if called by compressor
When a compressor is running, the pump or the supply fan is running.
3= ON/OFF: continuous operation type 2
When the unit is running in Chiller or Heat Pump or in STD-By or in
OFF, the pump or the supply fan is running.
4= Modulation: continuous operation type 1
When the unit is running in Chiller or Heat Pump the pump or the
supply fan is running. In std-by or remote OFF mode, the pump is
OFF.
5= Modulation: on if called by compressor
When a compressor is running, the pump or the supply fan is running.
6= Modulation: continuous operation type 2
When the unit is running in Chiller or Heat Pump or in STD-By or in
OFF, the pump or the supply fan is running.
0 6
CO 16