1592022750 Quick reference guide IC 200CX Rel. 1.1 25/05/2009
CO 37
Maximum unloading duration time to keep activated the Unloading
function from high temperature of the evaporator water inlet (See
unloading function).
0 250 Min
CO 38
Unloading compressor setpoint in chiller to prevent low temperature
of the evaporator water inlet (See unloading function).
-50
-58
70.0
158
°C
°F
Dec
int
CO 39
Unloading Differential to prevent low temperature of the evaporator
water inlet (See unloading function).
0.1
1
25.0
45
°C
°F
Dec
int
CO 40
Maximum unloading duration time to keep activated the Unloading
function from low temperature of the evaporator water inlet (See
unloading function).
0 250 Min
Condenser Unloading
CO 41
Unloading compressor setpoint. From temperature / pressure in
chiller mode (See unloading function).
0
0
50.0
725
Bar
psi
Dec
int
CO 42
Unloading Differential. From temperature / pressure in chiller mode
(See unloading function).
0.0
0
14.0
203
Bar
Psi
Dec
int
CO 43
Unloading compressor setpoint. From temperature / pressure in HP
mode (See unloading function).
0
0
50.0
725
Bar
psi
Dec
int
CO 44
Unloading Differential. From temperature / pressure in HP mode (See
unloading function).
0.0
0
14.0
203
Bar
Psi
Dec
int
CO 45
Maximum unloading duration time from temperature/pressure control. 0 250 Min
CO 46
Number of steps for circuit with active unloading
1= 1
st
step
2= 2
nd
step
3= 3
rd
step
1 3
CO 47
Minimum ON time of the capacity step after the unloading function
start (only for capacity compressor)
0 250 Sec
Compressor liquid injection
CO 48
Setpoint of the solenoid valve (on) of the liquid injection
0
32
150
302
°C
°F
Dec /
int
int
CO 49
Setpoint of the solenoid valve (off) of the liquid injection 0.1
1
25.0
45
°C
°F
Dec
int
Load management in neutral zone
CO 50
Maximum working time in neutral zone without steps insertion 0 250 Min 10 Min
CO 51
Maximum working time in neutral zone without steps rotation 0 999 Hr 1Hr
Pump down to time
CO 52
Maximum time for the activation of the pump-down during the
switching off
CO58 = 0 Not enabled
0 250 Sec
CO 53
Maximum time for the activation of the pump-down during the
switching on
CO59 = 0 Not enabled
0 250 Sec
Compressor inverter controlled
CO 54
Time at maximum speed during compressor start up
0 250 sec
CO 55
Minimum value of the proportional output at compressor start up
0 100 %
CO 56
Minimum interval time of the capacity variation at compressor start up 1 250 sec
CO 57
Value under wich starts counting time CO58 0 100 %
CO 58
Maximum working time of the compressor with percentage lower than
CO57
0 250 Min 10 Min
CO 59
Time of forcing the compressor digital scroll to the maximum power
0 250 sec 10sec
CO 60
Maximum working time for compressors rotation
0 999 Hr 1Hr

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the dixell IC200CX Series and is the answer not in the manual?

dixell IC200CX Series Specifications

General IconGeneral
Branddixell
ModelIC200CX Series
CategoryTemperature Controller
LanguageEnglish

Related product manuals