1592022750 Quick reference guide IC 200CX Rel. 1.1 25/05/2009
CO 61
Minimum value of the proportional output digital scroll 10V
compressor 1
0 CO62
%
CO 62
Maximum value of the proportional output digital scroll 0÷10V
compressor 1
CO61
100 %
CO 63
Minimum value of the proportional output digital scroll 10V
compressor 2
0 CO64
%
CO 64
Maximum value of the proportional output digital scroll 0÷10V
compressor 2
CO63
100 %
CO 65
Minimum interval time of the capacity variation
1 250 sec
Tandem function
CO 66
Maximum working time for compressors rotation 0 250 Min
Solenoid valve water side
CO 67
Delay time for compressor activation starting from solenoid valve
activation
0 250 Min
CO 68
Delay time for solenoid valve deactivation starting from compressor
deactivation
0 250 Min
Unbalanced compressors
CO 69
Compressor 1 weight 0 100 %
CO 70
Compressor 2 weight 0 100 %
CO 71
Maximum numbers of start up per hour
0= function disabled
0 60
Modulating evaporator water pump
CO 72
Probe selection (Pb1..Pb6) for modulating evaporator water pump in
chiller
0 6
CO 73
Probe selection (Pb1..Pb6) for modulating evaporator water pump in
heat pump
0 6
CO 74
Set point for modulating evaporator water pump in chiller -50.0
-58
0
0
70.0
158
50.0
725
°C
°F
Bar
Psi
Dec
Int
Dec
int
CO 75
Proportional band for modulating evaporator water pump in chiller 0.1
1
0.1
1
25.0
45
14.0
203
°C
°F
Bar
Psi
Dec
Int
Dec
int
CO 76
Set point for modulating evaporator water pump in heat pump -50.0
-58
0
0
70.0
158
50.0
725
°C
°F
Bar
Psi
Dec
Int
Dec
int
CO 77
Proportional band for modulating evaporator water pump in heat
pump
0.1
1
0.1
1
25.0
45
14.0
203
°C
°F
Bar
Psi
Dec
Int
Dec
int
CO 78
Minimun value of the signal for the modulation of the pump
0
CO
79
%
CO 79
Maximun value of the signal for the modulation of the pump CO
78
100 %
CO 80
Time at maximum speed when the pump is activated 0 250 sec
CO 81
Value of the signal when the compressor is OFF or when the unit is in
STD-BY or remote OFF
0 100 %
CO 82
Time at maximum speed during the switching off of the pump 0 250 sec
Modulating condenser water pump

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the dixell IC200CX Series and is the answer not in the manual?

dixell IC200CX Series Specifications

General IconGeneral
Branddixell
ModelIC200CX Series
CategoryTemperature Controller
LanguageEnglish

Related product manuals