Digital Monitoring Products, Inc. | 734 Installation and Programming Guide 19
Activate Zone 2 Bypass
Select YES to activate the zone2 bypass operation. Selecting
NO allows standard zone operation on zone2. The default is
NO.
If the door being released by the 734 module is protected
(contact installed), a programmable bypass entry/exit timer
can be provided by connecting its contact wiring to the 734
module zone2. When the onboard Form C relay activates
and the user opens the door connected to zone2, the zone
is delayed for the number of seconds programmed in ZONE
2 BYPASS TIME allowing the user to enter/exit during an
armed period.
If zone2 does not restore (door closed) within the
programmed time, the piezo sounds every other second
during the last ten seconds. If zone2 restores prior to the
end of the programmed time, the piezo silences. If the zone
does not restore before the programmed time, the 734 ends
the bypass and indicates the open or short zone condition to
the panel.
ACTIVATE ZONE2
BYPASS? NO YES