XR200/XR2400F Programming Guide Digital Monitoring Products
11
3 - COMMUNICATION
3.8 Defer Test Time
Select YES to allow the programmed test report to be deferred if the panel
communicates with a receiver within the time set in Test Frequency. Select NO to
send the test report as programmed regardless of previous panel communication.
3.9 Test Frequency
Allows you to set how often the panel sends a test report to the SCS-1 receiver.
Enter from 1 to 60 days. This prompt is not displayed if Defer Test Time is NO.
3.10 Test Time
Press COMMAND to show the enter test time display. Enter the time of day the
panel sends the test report to the SCS-1 Receiver. Use entries between 12:00 to
11:59 and then choose AM or PM. When Defer Test Time is set to NO, this option
allows you to program the day of the week the test report is sent. Choose one
day of the week or all days.
TEST FREQ: 1
TEST TIME
0 : 0 0 A M P M
TEST DAY: ALL
DFR TEST NO YES