14.7.1 Wireless
Select YES if you are programming a wireless zone. Press the COMMAND key to
continue with wireless programming.
14.7.2 Check-in Time
You can set transmitters to check in automatically every 10, 30, or 60 seconds or
not at all. To change the default of 60 seconds, press any Select key to display
the default display of NONE 10 30 60. Press the Select key under the check-in
time you want for this zone.
14.7.3 Internal Contact
Select YES to use an internal contact on the wireless transmitter. Select NO to
use an external contact. When NO, the following two prompts are displayed.
14.7.4 End-of-Line
Select YES to supervise an external contact connected to the transmitter. At the
contact, install a 2.2k Ohm End-of-Line resistor in parallel for Normally Open
contacts and in series for Normally Closed contacts.
14.7.5 Normally Open
Select NO if the contact connected to the transmitter is a Normally Closed type.
14.8 Alarm Action
This option allows you to change the standard definitions of any Zone Type. When
the Zone Type is specified, the Alarm Action for that zone is stored in memory.
If the Zone Type is Blank, Night, Day, Exit, Auxiliary 1, or Auxiliary 2 it is a non-24
hour zone and the Alarm Action programing begins with Disarmed Open.
If the Zone Type is Fire, Panic, Emergency, or Supervisory it is a 24-hour zone that
is always armed and the Alarm Action programming begins with Armed Open.
The Fire Verify Zone Type functions the same as Fire Type, with the following
exceptions: When a Fire Verify zone initiates an alarm, the panel performs a
Sensor Reset. If any Fire Verify zone initiates an alarm within 120 seconds after
the reset, an alarm is indicated. If an alarm is initiated after 120 seconds, the
cycle is repeated and a zone fault report is sent to the receiver.
Do NOT program Fire Verify Zone Types for Zone Retard.
14.9 Disarmed Open
Defines the action taken by the panel when the zone is opened while the area is
disarmed. There are three actions to define:
Report to transmit Relay Output to activate Relay
Output action
You must also make these selections for the Disarmed Short, Armed Open, and
Armed Short zone conditions. Press COMMAND to continue. A description of each
selection is found on the following page.
DISARMED OPEN
ALARM ACTION . . .
NRM OPEN YES
E O L NO YES
INT CONT NO YES
WIRELESS NO YES
CHECK IN TM: 60
14 - ZONE INFORMATION