Digital Monitoring Products XT30/XT50 Installation Guide
8
INSTALLATION
6.7 XT30/XT50 Standby Battery Calculations
Standby Battery Power Calculations Alarm Current
XT30 Panel
XT50 Panel
Built-inNetwork(additionalcurrent)
ActiveZones1-9
ActiveZone10
2-WireSmokeDetectors
Panel Bell Output
x
x
x
x
x
125mA
145mA
145mA
1.6mA
4mA
0.1mA
______mA
______
______
______
______
______
Qty ______
Qty ______
Qty ______
1500mA
x
x
x
x
125mA
145mA
145mA
*2mA
30mA
0.1mA
Max.
______mA
______
______
______
______
______
______
263CDigitalCellularCommunicator x 13mA ______ Qty ______ x 13mA ______
263H HSPA+ Cellular Communicator x 24mA ______ Qty ______ x 28mA ______
1100DWirelessReceiver x 40mA ______ Qty ______ x 40mA ______
1100DHWirelessHighPowerReceiver x 160mA ______ Qty ______ 160mA ______
1100DIWirelessIn-LineReceiver x 30mA ______ Qty ______ 30mA ______
860RelayOutputModule(onerelayactive)
Allfourrelaysactive
x 34mA
138mA
______
______
Qty _______ x 34mA
138mA
______
______
7060/7160Thinline/7060AAqualiteKeypad x 72mA ______ Qty ______ x 87mA ______
7063/7163Thinline/7063AAqualiteKeypad x 85mA ______ Qty ______ x 100mA ______
7070/7170Thinline/7070AAqualiteKeypad
ActiveZones(EOLInstalled)
x 72mA
1.6mA
______
______
Qty ______
Qty ______
67mA
80mA
______
______
7073/7173Thinline/7073AAqualiteKeypad
ActiveZones(EOLInstalled)
x 85mA
1.6mA
______
______
7360ThinlineIconKeypad
7363ThinlineIconKeypad
x
x
60mA
73mA
______
______
Qty ______
Qty ______
x
x
67mA
80mA
______
______
7872GraphicTouchscreenKeypad
ActiveZones(EOLInstalled)
x 130mA
1.6mA
______
______
Qty ______ x 188mA
2.0mA
______
______
7873GraphicTouchscreenKeypad
ActiveZones(EOLInstalled)
x 130mA
1.6mA
______
______
Qty ______ x 188mA
2.0mA
______
______
708BusExtenderModule(onepair) x 20mA ______ Qty ______ x 20mA ______
710 Bus Splitter/Repeater Module x 30mA ______ Qty ______ x 30mA ______
714 Zone Expansion Modules
ActiveZones(EOLInstalled)
x
x
7mA
1.6mA
______
______
Qty ______
Qty ______
x
x
7mA
*2mA
______
______
712-8 Zone Expansion Module
ActiveZones(EOLInstalled)
x
x
17mA
1.6mA
______
______
Qty ______
Qty ______
x
x
17mA
*2mA
______
______
714-8, 714-16 Zone Expansion Module
ActiveZones(EOLInstalled)
x
x
20mA
1.6mA
______
______
Qty ______
Qty ______
x
x
20mA
*2mA
______
______
715 Zone Expansion Module
ActiveZones(EOLInstalled)
2-Wire Smokes
x
x
x
7mA
4mA
.1mA
______
______
______
Qty ______
Qty ______
Qty ______
x
x
x
7mA
*30mA
.1mA
______
______
______
715-8, 715-16 Zone Expansion Modules
ActiveZones(EOLInstalled)
2-Wire Smokes
x 20mA
4mA
.1mA
______
______
______
Qty ______ x 20mA
*30mA
.1mA
______
______
______
734WiegandInterfaceModule
ActiveZones(EOLInstalled)
x
x
15mA
1.6mA
______
______
Qty ______
Qty ______
x
x
15mA
*2mA
______
______
738A Ademco Wireless Interface Module x 75mA ______ Qty ______ x 75mA ______
738ZplusZ-WaveInterfaceModule x 40mA ______ Qty ______ x 45mA ______
763 Wi-Fi Module x 90mA ______ Qty ______ x 90mA ______
Aux.PoweredDevicesonTerminals7and11
OtherthanKeypadsandModules
______mA ______mA
Total Standby
Total Standby______mA x number of Standby Hours
needed
Total Alarm
*Basedon10%ofactivezonesinalarmcondition.
______mA
______ =
______mA
+
Total
Total Alarm
________mA-hours
________mA-hours
________mA-hours
X .001
=________Amp-hrs
______mA
Required