XT30/XT50 Installation Guide Digital Monitoring Products
17
COMPLIANCE
Central Station Burglar Alarm Units
ANSI/UL 1610
23.1 Central Station
Commercial Burglary is provided when the Check-in and Fail Time time is set to 3 minutes for Net or Cell
communication.
Note: The SecureCom Wireless text plan selected for the panel should match or exceed the programmed
Monthly Limit or additional cellular charges may apply.
Digital Dialer Central Station (DACT) service for commercial application can be provided by adding a listed
local audible signal appliance and placing the XT30 or XT50 panel into the Model 349A Attack Resistant
Enclosure.
23.2 Remote Disarm
REMOTE DISARM must be programmed as NO.
23.3 Central Station
MESSAGE TO TRANSMIT programming for zones must not be set to LOCAL (L).
23.4 Closing Wait
Automatic Bell Test and Opening/Closing must be set to YES to enable Closing Wait. Closing Wait provides
a delay time before a monitored system arms until the panel receives an acknowledgment of the closing
report from the central station receiver.
Household Fire Warning System
ANSI/UL 985 NFPA 72 Specications
24.1 Bell Output Denition
The bell output of the Model XT30/XT50 must be programmed to operate steady on burglary alarms and
temporal on re alarms. See the XT30/XT50 Programming Guide.
24.2 Household System
An alarm sounding device must be installed indoors so that it is clearly heard in all sleeping areas.
24.3 Household Fire Warning
Recognized limited energy cable must be used for connection of all initiating, indicating, and supplementary
devices.
24.4 Wireless Supervision Time
The Zone Information Supervision Time must be 3 minutes for re devices. See the XT30/XT50 Programming
Guide.
24.5 Wireless Fire Verication
When used, the Model 1161 and 1162 wireless smoke detectors must not be programmed as Fire Verication
(FV) zone type. See the XT30/XT50 Programming Guide.
24.6 Battery Standby
For UL listed applications, the panel must have 24 Hour battery standby operation. The Model 364 battery
should not be used for re installations.
24.7 Alarm Verication
Alarm Verication must only be enabled on smoke detectors that do not employ an integral alarm
verication feature.
24.8 Model 860
When using the Model 860 Relay Output, a re and non-re device must not share a relay.
24.9 Test Frequency
The Test Frequency option must be programmed to send a report at least once every 30 days.
California State Fire Marshal Specications
25.1 Bell Output Denition
The bell output of the Model XT30/XT50 must be programmed to operate steady on burglary alarms and
temporal on re alarms.

Table of Contents

Other manuals for DMP Electronics XT30

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the DMP Electronics XT30 and is the answer not in the manual?

DMP Electronics XT30 Specifications

General IconGeneral
BrandDMP Electronics
ModelXT30
CategoryControl Panel
LanguageEnglish

Related product manuals