XT30/XT50 Installation Guide Digital Monitoring Products
17
COMPLIANCE
Central Station Burglar Alarm Units
ANSI/UL 1610
23.1 Central Station
Commercial Burglary is provided when the Check-in and Fail Time time is set to 3 minutes for Net or Cell
communication.
Note: The SecureCom Wireless text plan selected for the panel should match or exceed the programmed
Monthly Limit or additional cellular charges may apply.
Digital Dialer Central Station (DACT) service for commercial application can be provided by adding a listed
local audible signal appliance and placing the XT30 or XT50 panel into the Model 349A Attack Resistant
Enclosure.
23.2 Remote Disarm
REMOTE DISARM must be programmed as NO.
23.3 Central Station
MESSAGE TO TRANSMIT programming for zones must not be set to LOCAL (L).
23.4 Closing Wait
Automatic Bell Test and Opening/Closing must be set to YES to enable Closing Wait. Closing Wait provides
a delay time before a monitored system arms until the panel receives an acknowledgment of the closing
report from the central station receiver.
Household Fire Warning System
ANSI/UL 985 NFPA 72 Specications
24.1 Bell Output Denition
The bell output of the Model XT30/XT50 must be programmed to operate steady on burglary alarms and
temporal on re alarms. See the XT30/XT50 Programming Guide.
24.2 Household System
An alarm sounding device must be installed indoors so that it is clearly heard in all sleeping areas.
24.3 Household Fire Warning
Recognized limited energy cable must be used for connection of all initiating, indicating, and supplementary
devices.
24.4 Wireless Supervision Time
The Zone Information Supervision Time must be 3 minutes for re devices. See the XT30/XT50 Programming
Guide.
24.5 Wireless Fire Verication
When used, the Model 1161 and 1162 wireless smoke detectors must not be programmed as Fire Verication
(FV) zone type. See the XT30/XT50 Programming Guide.
24.6 Battery Standby
For UL listed applications, the panel must have 24 Hour battery standby operation. The Model 364 battery
should not be used for re installations.
24.7 Alarm Verication
Alarm Verication must only be enabled on smoke detectors that do not employ an integral alarm
verication feature.
24.8 Model 860
When using the Model 860 Relay Output, a re and non-re device must not share a relay.
24.9 Test Frequency
The Test Frequency option must be programmed to send a report at least once every 30 days.
California State Fire Marshal Specications
25.1 Bell Output Denition
The bell output of the Model XT30/XT50 must be programmed to operate steady on burglary alarms and
temporal on re alarms.