Doble TDR900 User Guide
72A-2612-01 Rev. A 09/06
46
Figure 37. Test Results – Main Contacts Sub-tab
The test results are checked against specifications, if available in the breaker test plan. In
the results in Figure 37, a Close measurement on an overall (OCB) test is compared with
the 142.0 ms maximum specified in the test plan. Each value is acceptable, and a green
check mark (tick mark) is shown next to the result.
Figure 38. Symbols for “OK” and “Investigate: