dormakaba ED900 Setup and Troubleshooting Instructions Chapter 10
. Set power fail closing speed
1 Power fail closing
speed
potentiometer
2 Control board
Fig. 10.9.1 Power fail closing speed potentiometer
1
2
o
1
2
Fig. 10.9.2 Power on switch
1 Power on switch
2 Terminal board
.. Power fail closing speed
potentiometer.
• Single turn
• Factory setting: fully CCW
• CCW increases closing speed.
• CW decreases closing speed.
• /" [- mm] flat blade screwdriver
required for adjustment.
.. Setting door closing speed upon
power failure.
. Turn power switch OFF.
. Manually open door to ° angle and let
it close.
. If door closes in less than seconds, turn
potentiometer / turn CW and retry
test.
. Continue retrying test after
potentiometer adjustment until the door
closing time is a minimum of seconds.
NOTICE
Error message E73:
If door closes in less than three
seconds, error message E 73
(System error 3, braking circuit) will
be displayed.
Reference: Appendix B,
Troubleshooting.