W2940305    Rev 07    8/2019    Dover Fueling Solutions  31 
4.2.5.3  Changing the Pulse Ratio 
NOTES: The following table shows the setting for units without price displays.  Units with price 
displays will look slightly different as they typically utilize all three displays. 
  The Pulse Output mode cannot be used in conjunction with the serial communication 
interface.  
  Follow the step by step instructions below to change the pulse ratio from 100:1 to a 
different ratio. 
  When the pulse output ratio is changed, the display resolution is automatically adjusted to 
match the pulse output resolution so that a higher resolution is not implied at the 
dispenser than what is being recorded by the fuel management system. For example, 
when the pulse output ratio is set to 1000:1, the volume display shows three decimal 
places. When the pulse output ratio is 100:1, the volume display shows two decimal 
places. 
Enter Configuration Mode 
Step IRC Command 
olume 
Display 
Status 
Display 
1  Service engineer sign 
on 
Press <ENTER> 
PASS 1  [blank] 
2  Enter default service 
engineer password 
Type <111> & Press <ENTER> 
PASS 2  [blank] 
3 Re-enter default 
service engineer 
password 
Type <111> & Press <ENTER> 
[alternating 
software 
version & date] 
F  - - 
 
Change the Pulse Ratio – Gallons (Skip to Step 10 if Liters) 
4  Go to volume function  Type <19> & Press <ENTER>  - - - - - -  F 19 
5  Go to sub-function 
level 
Press <ENTER> again 
3  19.10 
6  Go to gallons pulse 
ratio sub-function 
Type <25> & Press <ENTER> 
3  19.25 
7  Clear display   Press <#>  [blank]  19.25 
8  Enter –pulse ratio 
choice 
Type the value of the pulse ratio 
choice below and then press 
<ENTER> 
1 = 1 pulse per gallon 
2 = 10 pulses per gallon 
3 = 100 pulses per gallon 
4 = 250 pulses per gallon 
5 = 500 pulses per gallon 
6 = 1000 pulses per gallon 
[desired value]  19.25 
9  Return to function level  Press <ENTER> again  - - - - - -  F 19 
 
- Additional Steps Are Continued on Next Page -