W2940305    Rev 07    8/2019    Dover Fueling Solutions  79 
E.9  Pulse Output Interface Option Settings 
  The following functions/sub-functions are used to configure the pulse output interface 
option. These settings should be set at the factory when the pulse output option is 
ordered. The only function typically requiring any modification is selection of the desired 
pulse output resolution. (Note: The “MPI” acronym in the sub-function descriptions stands 
for “Mechanical Pump Interface” which is equivalent to Pulse Output Interface.) 
  Reference the note at the base of the table regarding pulse resolution settings for liters. 
Sub-function Description  Setting 
Enable Pulse Output 
41.01  Pulse Output – Side A  2 = enabled 
Set Pulse Resolution - Gallons* 
19.25  Gallons Pulse Resolution Output 
1 = 1:1  4 = 250:1 
2 = 10:1  5 = 500:1 
3 = 100:1  6 = 1000:1 
Enable AC Authorization Input 
27.00  Local Authorization – Side A  0 = Disabled (set for MPI authorization) 
27.01  MPI Authorization – Side A  6 = enabled 
Enable Reset Complete 
41.03  MPI Reset Complete – Side A  10 = enabled 
*Note: For pulse output for liters, substitute the following sub-function and settings below. 
Set Pulse Resolution - Liters 
19.15  Liters Pulse Resolution Output 
1 = 1:1  3 = 100:1 
2 = 10:1  4 = 250:1 
 
Note:  If the pulse output is used to supply pulses to a secondary monitoring system (i.e. a tank 
monitor), but the control system is authorizing the dispenser via the serial current loop with 
F01 set to “1” (i.e. an iX Fleet system), the F41.01 must be enabled and F19.25 (gallons) or 
F19.15 (liters) must be set to the desired pulse ration.  The other pulse output setting are 
ignored in this serial connection mode.