5.3.4 Times / delay for pumps
In this menu you set the times and delays which are general for all pumps and different functions in
the pumping station.
Start delay– Signal delay for starts of pump when startlevel is reached, for ex when there is
turbulance on the surface of the pump pit.
Stop delay– Signal delay for stop of pump at stop level.
Min. Time starts* – Minimum time between start of pumps.
Min. Time stops **– Minimum time between stop of two pumps.
Switch time – Time delay between stop of pump with fault and start of next pump in the alternation
cycle
Backup running time Level switch operation – when only level switches are used to control de level
in the sump.
Min time starts Min. Time starts is the starts time delay between the first and the second pump when
the inflow is larger than one pumps capacity and there is need for a second pump to start.
Min time stopps Min. Time stops is the time delay between the stop of the first and the second pump
when two pumps are running.