5.4 Station settings
All setting in this menu are general setting for the pump station .
5.4.1 Alternation type of pumps
The controller has two different ways of handling the alternation of the pumps:
1. Cyclic – witch means that the pumps alternate in a cyclic way, one after another. This means
that in the first cycle they start with pumps 1,2,3 and in the next cycle wirh pumps 2,3,1.
2. Running time – which means that the pump that has the lowest running time starts first. This
means that the pumps will have about the same running times.
The second setting decides if the next pump in the alternation cycle shall start when the working pump
has an fault or not.
- if you set ”alternation on fault” to Yes the next pump will start with a short time delay when the
working pump has a fault.
- if you set “alternation on fault ” to No the next pump will wait until the start level is reached before
it starts.
5.4.2 Level alarm settings (Low and high level alarms)
In this menu the level alarms for the level sensor are set. These alarms only show how the levels in the
station are, but control no pumps