34
VAPOR-LOGIC
®
VERSION 6 INSTALLATION AND OPERATION MANUAL
INSTALLATION
Step 2 – Setup
Table 30-1:
Settings menu (continued)
Menu item Default value
Minimum
value
Maximum value Units Notes
Units inch-pound -- -- --
inch-pound -- -- -- --
SI units -- -- -- --
Idle Time-Out -- -- -- --
Idle Time-Out 5 1 120 Minutes
Select number of minutes the touchscreen display
remains idle before returning to the Home screen.
Brightness -- -- -- --
Adjust Brightness 60 10 100 % Use 100% brightness outdoors.
Clean Screen 30 30 30 Seconds
Touch input will be disabled for 30 seconds so the
user can wipe it with a soft cloth.
Capacity Calibration -- -- -- --
Capacity Calibration 100 0 245 %
Changing the capacity calibration setting changes
reported, not actual, humidifier output
Security
Require Passcode No No Yes --
Set Passcode 0000 0000 9999 --
Enter four digits, numbers only, and define the time-
out period (minutes of inactivity before Vapor-logic
reverts to read-only mode).
The default passcode is 0000.
Passcode Time-Out 5 1 120 Minutes
Backup / Restore Settings
Backup to USB -- -- -- --
Humidifier settings can be backed up to or restored
from a USB flash drive
Restore from USB -- -- -- --
Reset to Defaults -- -- -- --
CAUTION
These actions cannot be reversed.
Reset to Defaults -- -- -- --
Select this if you want to reset all humidifier settings
to factory defaults
Reset Ignition Counts -- -- -- -- Select this if you want to reset the GTS ignitor counts