33
VAPOR-LOGIC
®
VERSION 6 INSTALLATION AND OPERATION MANUAL
INSTALLATION
Step 2 – Setup
Table 30-1:
Settings menu (continued)
Menu item Default value
Minimum
value
Maximum value Units Notes
Communication Type Modbus -- -- --
BACnet MS/TP -- -- -- --
Comm Channel 38400 19200 76800 --
BACnet MS/TP
Settings
-- -- -- --
Device Instance 255 0 4194303 --
Max Masters 127 1 127 --
MAC Address 1 0 127 --
Max Info Frames 1 1 127 --
BACnet IP -- -- -- --
Device Instance 255 0 4194303 --
UDP port (47808) 47808 1024 65535 --
Modbus -- -- -- --
Modbus Baud Rate 19200 4800 38400 --
Modbus Address 99 0 255 --
LonTalk -- -- -- --
Display
Date and Time -- -- -- --
Set Date 1999 -- -- --
Set Time 0:00 0:00 23:59 -- 24 hour clock
Humidifier Info -- -- -- --
Unit Name order-specific 1 20 Characters
Press the edit icon to edit the name of the
humidifier. This name is not communicated by
BACnet, LonTalk or Modbus.
Model order-specific -- -- -- Displays humidifier model
Serial Number order-specific -- -- -- Displays humidifier serial number
Factory String order-specific -- -- -- Displays as-shipped configuration
Current String -- -- -- -- Display current configuration string
Firmware Version -- -- -- --
Displays current firmware version of Vapor-logic
control board and date of firmware release.
Display Version -- -- -- --
Displays current firmware version of board internal
to touch screen display and date of firmware
release
Language English -- -- --
English -- -- -- --