Table 39-1:
Status screen
Note: Your system might not have all of the items listed in this table (Pages 39 and 42).
Menu item Default value
Minimum
value
Maximum
value
Units Notes
Mode Standby -- -- --
Operating mode of humidifier. Choose from Auto, Standby, or Drain.
• In Auto mode, the humidifier operates normally. All humidifier
components are monitored and controlled. If there is a call for
humidification, the system reacts.
• In Standby mode, the humidifier is offline. All humidity control inputs
appear but are not acted upon; however, if the tank temperature falls
below the freeze protect set point, the drain valve opens.
• In Drain mode, the automatic drain valve (if so equipped) opens and
the tank drains. All humidifier operation is suspended, and the drain
valve remains open until the unit is taken out of Drain tank mode.
• See the Diagnostics section for information about Test outputs and Test
run modes.
Space RH -- 0 100 %
RH set point 35 0 100 %
Input signal
-- 0 10 VDC
-- 0 20 mA
Dew point
-- 0 100 °F
-- -17 37 °C
Dew point set point
50 20 80 °F
10 -6 26 °C
Inlet pressure switch -- No water Water --
Steam demand -- 0 100 % Displays steam demand as a percent of capacity
Steam output -- 0 100 % Displays steam output as a percent of capacity
Steam production
-- 0 100,000 lbs/hr
-- 0 100,000 kg/h
Duct RH -- 0 100 %
Duct HL switch -- Open Closed --
Duct HL set point 80 5 95 %
Duct HL signal -- 0 20 mA
Tank temperature
-- -30 275 °F
-- -34 135 °C
Tank temp signal -- 0 2200 Ohms
Aux temperature
-- -20 160 °F
-- -29 71 °C
Aux temp signal -- 0 26 mA
Continued
Status screen
OPERATION