EasyManua.ls Logo

DriSteem VAPOR-LOGIC Version 6 - Page 89

DriSteem VAPOR-LOGIC Version 6
96 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
85
VAPOR-LOGIC
®
VERSION 6 INSTALLATION AND OPERATION MANUAL
Troubleshooting guide
Table 85-1:
Troubleshooting guide (continued)
Draining issues
Issue Possible causes Actions
Alerts:
Tank not draining
Tank drain outlet If the humidifier tank drain outlet is plugged, clean.
Water detection probes Clean probe or replace probe rod assembly.
Drain valve wiring Check drain valve wiring.
Check to be sure drain valve is wired to Terminal P17 (drain)
on control board.
Reset Vapor-logic.
Fill valve Check for voltage present at the valve. If present, clean or
replace valve.
Replace fill valve if water is leaking through.
System programmed for manual drain Run a test cycle to see if the system activates drain output.
Drain line backing up with water
Drain line plugged
Insufficient drain line pitch.
Insufficient drain line size. See tank manual for drain piping
size and pitch requirements.
Unit does not perform
automatic drain sequence
Automatic drain is disabled Go to Settings menu to verify that auto drain/flush is enabled.
Drain fault, plugged drain valve, or plugged
drain pipe
Clean drain valve piping.
Malfunctioning automatic drain sequence Go to Settings menu and check auto drain/flush settings.
No power to the automatic drain valve Check if 24 VAC is present at terminal block P17 (drain) and
at drain valve.
Defective automatic drain valve If voltage is present at the valve and it still does not open,
replace valve.
Unit does not perform
end-of-season drain
Input signal always has a demand Reduce demand signal.
• Vapor-logic
setup Verify in Settings menu Vapor-logic is set for end-of-season
drain.
Drain valve Valve not wired, or incorrectly wired, to control board.
Check 24 VAC across valve coil during test cycle.
Alert:
Drain sensor out of range
Signal outside of 4-20mA Check P6 voltage from CS2 to ground (2-10vdc)
• Replace transmitter if no voltage output
Check voltage on P6 from 21vdc to ground is 21vdc. If not,
re-check terminals for all field connections.
Continued
TROUBLESHOOTING

Table of Contents

Related product manuals