86
VAPOR-LOGIC
®
VERSION 6 INSTALLATION AND OPERATION MANUAL
Troubleshooting guide
Table 86-1:
Troubleshooting guide (continued)
Heating issues
Issue Possible causes Actions
Alert:
Tank temperature sensor
failed
Open, shorted, or incorrect wiring of sensor Check wiring terminals for correct wiring and voltages.
1000 Ohms = 68 °F (20 °C); 1702 Ohms = 212 °F (100 °C).
Humidifier interlock switches and/or over-
temperature thermostat
Verify that switch or thermostat is wired.
Verify interlock switch is set correctly and humidifier cover is on.
Reset over-temperature thermostat if tripped.
Alert:
Tank overtemp
Unit has overheated; temperature is at 25 ºF
(14 ºC) over boiling temperature
Check for proper water level in tank.
Faulty sensor Replace sensor.
Reduced or not output
(even though water level is
correct)
Dirty heat exchanger • Clean.
Dirty burners
Low gas pressure
Clean or adjust as appropriate. See tank manual for instructions.
Tank does not heat up. Over-temperature thermostat switch located
under heater wiring cover tripped
Reset thermostat switch.
Humidifier cover interlock switch (select
models only)
Humidifier cover not wired; adjust interlock switch.
Incorrect or nonexistent control voltage Check for proper supply voltage on electrical diagram.
Verify proper transformer voltage characteristics.
Verify proper wiring of transformer.
Check for control circuit voltage on electrical diagram. If voltage
is not present, troubleshoot boards and wiring system for
potential short circuit.
Incorrect or nonexistent supply voltage to the
unit
Check main line fuse.
Check main line safety switch.
Check heater fuses and wiring diagram.
Duct RH above high limit set point Check for duct airflow.
Verify operation of duct high limit switch or transmitter.
No demand signal Check signal by others.
Check for miswired connection.
Verify in the Settings menu that humidifier is configured for
demand signal.
Humidifier is in Standby mode Change mode to Auto.
Humidifier tank has proper
water level and is always
warm.
• Aquastat This is normal; the aquastat is maintaining a certain tank water
temperature within range of 40 ºF to 180 ºF (4 ºC to 82 ºC).
Readjust aquastat temperature to a lower set point.
Continued
TROUBLESHOOTING