EasyManua.ls Logo

DriSteem XT-10 - Page 64

DriSteem XT-10
72 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page 62 • DRI-STEEM XT Series Electrode Steam Humidifier Installation, Operation, and Maintenance Manual
Troubleshooting (continued)
Table 62-1:
Problem/possible cause/action
Problem Possible cause Action
No readable information
on display
No power or incorrect
voltage to processor board
Check main power supply.
Reset control transformer circuit breaker if tripped.
Modular communication
cable is disconnected.
Connect modular cable.
Humidifier does not
energize; steam cylinder
does not heat up
Non-existent supply voltage
to humidifier
Check main line fuse.
Check main line safety switch.
Verify terminal block electrical connections.
Verify contactor electrical connections.
Non-existent control voltage Check for proper supply voltage per wiring diagram.
Verify proper wiring of multi-tap transformer.
Verify terminal block electrical connections.
Check for control circuit voltage, 24 VAC. If voltage is not present, check transformer circuit breaker.
Reset if needed by pressing On/Off switch on display panel.
Check door interlock switch continuity.
H-H terminals are open. Check if auxiliary limit controls are not allowing system to operate, e.g., high limit humidistat, airflow
proving switch, etc. Reset, replace, or calibrate as needed. Jumper H-H if auxiliary limit controls are
not used.
Transmitter or humidistat
faults:
• Open, shorted, or incorrect
wiring of transmitter or
humidistat
• Signal is incorrect, out of
range, or miswired.
• Ground loop
• Control signal exceeded
the range limits. Correct
signals are 4 to 20 mA, 0
to 135 ohms, or 0 to 10
VDC.
Check DC supply voltage terminals of RH transmitter, VAV humidity transmitter, or humidistat:
Terminal 13: 21 VDC; Terminal 23: GND
If there is no output 4 to 20 mA, replace transmitter. Transmitter by others may not be compatible.
Consult DRI-STEEM.
Isolation control board by others may not be compatible. Consult DRI-STEEM.
Recalibrate if there is a calibration error: Normal range 4 to 20 mA = 0 to 100% RH;
12 mA = 50% RH
Measure for normal 0 to 10 VDC or 4 to 20 mA control signal.
Reduced or no output
(even though water
level is correct)
Malfunctioning control
system
Check if auxiliary limit controls are not allowing system to operate, e.g., high limit humidistat, airflow
proving switch, etc. Reset, replace, or calibrate as needed. Jumper H-H if auxiliary limit controls are
not used.
Check fuse in power circuit. If open, replace fuse with equal fuse.
Steam cylinder
malfunctioning
Verify that proper voltage is being applied to the steam cylinder.
Check current through electrode wires.
If power components are not functioning, replace.
Steam cylinder failure Improper wiring Verify proper voltage applied to steam cylinder.
Verify proper electrical connections.
Mineral buildup on steam
cylinder electrodes
Inspect steam cylinder for severe mineral buildup on or around electrodes. If present, increase
cleaning frequency or replace steam cylinder.
Steam cylinder electrode
corrosion
Inspect electrodes for surface corrosion or pitting. This is usually caused by a high chloride level in the
supply water. Test water and consult DRI-STEEM for advice.
More on the next page
XT_IOM_Jan_2008.pdf 64 11/19/2009 10:13:40 AM

Related product manuals