EasyManua.ls Logo

DriSteem XT-10 - Page 65

DriSteem XT-10
72 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
DRI-STEEM XT Series Electrode Steam Humidifier Installation, Operation, and Maintenance Manual • Page 63
Table 63-1:
Problem/possible cause/action
Problem Possible cause Action
Unit does not fill with
water.
No water supply to fill valve Verify that manual water supply valve is open and that pressure exists.
Check if water supply line strainer is plugged. Clean strainer or replace.
Verify fill valve electrical connections.
Clean or replace fill valve strainer if plugged.
Unit control is not on Press On/Off switch on display panel.
Verify transformer electrical connections.
Malfunctioning fill valve Cycle fill valve while in Service mode. If fill valve does not open:
Verify fill valve electrical connections.
Verify proper 24 VAC (terminals 2 and 5) to fill valve. If voltage is present and valve does
not open, replace valve.
Humidifier is in end-of-
season drain mode.
Check for humidification demand signal at control board. See control wiring diagrams for terminal
check points.
Fill valve does not close. Malfunctioning level control
system
Check that high water sensor electrical plug is fully engaged.
Check water conductivity. Water conductivity must be at least 125 μS/cm
. Add sodium bicarbonate
through steam outlet on top of steam cylinder to increase. Start with ¼ tablet. Consult DRI-STEEM for
further advice.
Fill valve is stuck. Check for control voltage across fill valve coil (terminals 2 and 5 on control terminal strip).
Check if there is an obstruction that does not allow valve to seat properly. Clean or replace valve as
needed.
Drain valve is open. Clean or replace drain valve if an obstruction in the valve does not allow complete closure.
Replace broken or weak return spring on drain valve.
Fill valve cycles on and
off frequently (several
times per minute)
Malfunctioning level control
system
Check water conductivity. Water conductivity must be at least 125 μS/cm
. Add sodium bicarbonate
through steam outlet on top of the steam cylinder to increase. Start with ¼ tablet.
Consult DRI-STEEM for further advice.
Drain valve not fully closed If an obstruction does not allow drain valve to fully close, clean valve.
Replace broken or weak return spring on drain valve.
Unit does not perform
autodrain sequence
No power to automatic drain
valve
Verify drain valve electrical connections.
Check if 24 VAC is present at the internal controller board terminals 3 and 6 for drain valve.
Drain fault, plugged drain
valve, or plugged drain pipe
Check drain valve piping.
Defective automatic drain
valve
If voltage is present at valve and it still does not open, replace valve.
Unit does not perform
end-of-season drain
Input signal always has a
demand
Reduce demand signal.
Drain valve Verify drain valve electrical connections.
Verify drain valve is wired correctly to control board.
Check 24 VAC across valve coil during test cycle (terminals 3 and 6 on control terminal strip).
More on the next page
Troubleshooting (continued)
XT_IOM_Jan_2008.pdf 65 11/19/2009 10:13:40 AM

Related product manuals