Operation
Eaton 9130 700/3000 VA UPS User’s Guide 164201718—Rev 7 www.eaton.com/powerquality 30
Number of Battery Strings [0] [1] [2] … [10]
See “Configuring the UPS for EBMs”on page 36.
1
Battery Charge Mode [ABM Cycling] [Constant] ABM Cycling
Temperature Compensated Charging [Enabled] [Disabled]
If Disabled, the default charger voltages for 25C
(77F) are assumed.
Enabled
Battery Charge % to Restart [Not Checked] [10] [20] … [100]
If a percentage is selected, automatic restart (if
enabled) occurs when the battery's charge reaches
the selected level.
Not Checked
Battery Low Alarm [Immediate] [2 min] [3 min] [5 min]
The “Battery Low”alarm triggers when the set
amount of backup time (approximately) remains in
the batteries. If set to Immediate, the alarm
activates at the same time as the “UPS on Battery”
notice.
3 min
Automatic Battery Support Tests [Enabled] [Disabled]
See “Running Automatic Battery Tests”on
page
36.
Enabled
Ambient Temperature Warning [Enabled] [Disabled] Enabled
Predictive Maintenance Notices [Enabled] [Disabled] Enabled
Remote Emergency Power-off (REPO)
Input Polarity
[Open] [Closed] Open
Logic Power Off [0] [1...120 min]
See “Logic Power Off” on page 33.
0 min
Table 3. User Settings (Continued)
Description Available Settings Default Setting
NOTE * See “Configuring Bypass Settings”on page 34.
NOTE ** The cXSlot Signal setting is for a communication card. The cXSlot Serial setting is for the relay card.