Specifications
Eaton 9130 700/3000 VA UPS User’s Guide 164201718—Rev 7 www.eaton.com/powerquality 64
625/563 30 112 219 279 401
PW9130L3000R-XL2U / PW9130L3000R-XL2US
3000/2700 3 20 37 53 71
2250/2025 5 27 54 80 106
1500/1350 10 49 89 123 164
750/675 28 105 183 264 358
PW9130G3000R-XL2U / PW9130G3000R-XL2UEU / PW9130i3000R-XL2U / PW9130i3000R-XL2US
3000/2700 4 19 34 53 69
2250/2025 5 29 53 79 103
1500/1350 9 45 84 122 165
750/675 27 102 175 263 344
Table 27. Battery Runtimes (in Minutes) at 100% Load (Tower Models) PF0.9
Tower Models
Load (VA/Watts) Internal Batteries + 1 EBM + 2 EBMs + 3 EBMs + 4 EBMs
PW9130L700T-XL
700/630 5 N/A N/A N/A N/A
525/473 8 N/A N/A N/A N/A
350/315 15 N/A N/A N/A N/A
175/158 33 N/A N/A N/A N/A
PW9130i700T
700/630 5 N/A N/A N/A N/A
525/473 8 N/A N/A N/A N/A
350/315 14 N/A N/A N/A N/A
175/158 31 N/A N/A N/A N/A
PW9130L1000T-XL
1000/900 6 32 55 84 109
750/675 10 44 81 115 161
500/450 19 69 111 191 258
250/225 32 130 274 364 498
PW9130G1000T-XL / PW9130G1000T-XLEU / PW9130i1000T-XL
1000/900 6 32 51 82 100
750/675 9 43 80 108 158
500/450 19 68 111 193 246
250/225 30 124 272 368 483
PW9130L1500T-XL
1500/1350 5 23 48 71 92
1125/1013 8 34 72 97 130
750/675 14 64 113 167 224
375/338 31 121 234 335 367
PW9130i1500T-XL
Table 26. Battery Runtimes (in Minutes) at 100% Load (Rack Models) PF0.9 (Continued)
Rack Models
Load (VA/Watts) Internal Batteries + 1 EBM + 2 EBMs + 3 EBMs + 4 EBMs