Eaton 9130 700/3000 VA UPS User’s Guide 164201718—Rev 7 www.eaton.com/powerquality 65
1500/1350 6 25 46 69 90
1125/1013 8 32 69 96 126
750/675 14 62 112 172 222
375/338 29 115 218 335 374
PW9130L2000T-XL
2000/1800 11 42 76 111 149
1500/1350 16 63 116 158 213
1000/900 26 99 169 243 344
500/450 55 169 333 486 625
PW9130G2000T-XL / PW9130G2000T-XLEU / PW9130i2000T-XL
2000/1800 11 44 79 115 162
1500/1350 17 60 112 164 203
1000/900 28 96 168 258 336
500/450 55 169 336 490 608
PW9130L3000T-XL
3000/2700 6 22 51 64 90
2250/2025 9 39 69 105 120
1500/1350 16 63 105 162 218
750/675 39 139 231 320 441
PW9130G3000T-XL / PW9130G3000T-XLEU / PW9130i3000T-XL
3000/2700 6 21 52 66 94
2250/2025 9 38 67 102 128
1500/1350 16 60 100 169 215
750/675 40 139 226 311 444
NOTE Battery times are approximate and vary depending on the load configuration and battery charge.
Table 28. Battery Runtimes (in Minutes) at 100% Load (Rack Models) PF0.7
Rack Models
Load (VA/Watts) Internal Batteries + 1 EBM + 2 EBMs + 3 EBMs + 4 EBMs
PW9130L700R-XL2U / PW9130L700R-XL2US (Estimated runtimes)
700/490 14 55 102 148 175
525/368 20 77 140 179 239
350/245 32 124 189 282 414
175/123 64 200 395 552 739
PW9130L1000R-XL2U
1000/700 10 40 73 108 149
750/525 13 58 101 152 219
500/350 24 85 172 249 304
250/175 48 190 310 451 569
PW9130G1000R-XL2U / PW9130G1000R-XL2UEU / PW9130i1000R-XL2U / PW9130i1000R-XL2US
1000/700 10 40 78 110 150
Table 27. Battery Runtimes (in Minutes) at 100% Load (Tower Models) PF0.9 (Continued)
Tower Models
Load (VA/Watts) Internal Batteries + 1 EBM + 2 EBMs + 3 EBMs + 4 EBMs