Specifications
Eaton 9130 700/3000 VA UPS User’s Guide 164201718—Rev 7 www.eaton.com/powerquality 66
750/525 13 55 103 151 223
500/350 22 82 186 250 312
250/175 47 190 328 431 584
PW9130L1500R-XL2U / PW9130L1500R-XL2US
1500/1050 7 34 63 88 135
1125/788 11 44 84 129 210
750/525 18 79 148 207 267
375/263 38 167 278 475 540
PW9130i1500R-XL2U / PW9130i1500R-XL2US
1500/1050 7 32 61 98 128
1125/788 11 47 83 126 195
750/525 18 81 143 208 262
375/263 38 171 298 416 564
PW9130L2000R-XL2U / PW9130L2000R-XL2US
2000/1400 9 45 6 124 163
1500/1050 14 66 115 165 225
1000/700 26 101 185 251 343
500/350 52 197 353 481 629
PW9130G2000R-XL2U / PW9130G2000R-XL2UEU / PW9130i2000R-XL2U
2000/1400 10 46 83 118 163
1500/1050 13 64 118 170 221
1000/700 25 95 190 242 345
500/350 53 205 346 488 625
PW9130L2500R-XL2U (Estimated runtimes)
2500/2250 7 31 59 87 119
1875/1688 10 43 81 121 154
1250/1125 17 65 120 163 203
625/563 40 145 228 363 491
PW9130G2500R-XL2U / PW9130G2500R-XL2UEU (Estimated runtimes)
2500/2250 7 31 59 87 119
1875/1688 10 43 81 121 154
1250/1125 17 65 120 163 203
625/563 40 145 228 363 491
PW9130L3000R-XL2U / PW9130L3000R-XL2US
3000/2100 5 25 48 72 100
2250/1575 8 37 72 102 137
1500/1050 13 60 100 165 223
750/525 34 138 228 326 438
PW9130G3000R-XL2U / PW9130G3000R-XL2UEU / PW9130i3000R-XL2U / PW9130i3000R-XL2US
3000/2100 6 25 45 68 96
2250/1575 8 34 70 96 130
Table 28. Battery Runtimes (in Minutes) at 100% Load (Rack Models) PF0.7 (Continued)
Rack Models
Load (VA/Watts) Internal Batteries + 1 EBM + 2 EBMs + 3 EBMs + 4 EBMs