Eaton® 9390 (100–160 kVA) UPS Installation and Operation Manual 164201604—Rev F 128
TTaabbllee 77.. NNoottiicceess ((CCoonnttiinnuueedd))
MMeessssaaggee
HHoorrnn PPhhoonnee
RReellaayy LLoogg**
IInnddiiccaattiioonn
Bypass AC Under Voltage OK Off No No HA Condition Cleared
Bypass Phase Rotation
1
No No HA Information Only
Bypass Phase Rotation OK Off No No A Condition Cleared
Bypass Source Out of Tolerance
1
No No HA
Investigate UPS
Bypass Source Out of Tolerance OK Off
No No HA
Condition Cleared
Bypass Under or Over Frequency
1
No No HA Information Only
Bypass Under or Over Frequency OK Off No No HA Condition Cleared
Charger Off Command
1
No No HA
Information Only
Charger On Command
1
No No HA
Information Only
Charger Over Voltage or Current
1
No No HA
Information Only
Charger Tripped
1
No No HA
Information Only
Charger Tripped OK Off No No HA Condition Cleared
Check Battery
1
No No HA Information Only
Check Battery OK Off No No HA Condition Cleared
Check Modem
1
No No HA Information Only
Check Modem OK Off No No HA Condition Cleared
DC Link Over Voltage
1 1
No HA Information Only
DC Link Over Voltage OK Off No No A Condition Cleared
DC Link Under Voltage
1
No No HA Information Only
DC Link Under Voltage OK Off
No No HA
Condition Cleared
Emergency Transfer To Bypass
1
No No HA
Information Only
Emergency Transfer To Bypass OK Off No No A Condition Cleared
Input AC Over Voltage
1
No No HA Information Only
Input AC Over Voltage OK Off No No HA Condition Cleared
Input AC Under Voltage
1
No No HA Information Only
Input AC Under Voltage OK Off No No HA Condition Cleared
Input Phase Rotation
1
No No HA Information Only
Input Phase Rotation OK Off No No HA Condition Cleared
Input Under or Over Frequency
1
No No HA Information Only
Input Under or Over Frequency OK Off No No HA Condition Cleared
Inv Under or Over Frequency
1
No No HA Information Only
Responding to System Events