131 Eaton® 9390 (100–160 kVA) UPS Installation and Operation Manual 164201604—Rev F
TTaabbllee 88.. SSttaattuuss ((CCoonnttiinnuueedd))
MMeessssaaggee
HHoorrnn PPhhoonnee
RReellaayy LLoogg**
IInnddiiccaattiioonn
Rectifier Phase L1 Current Limit No No No H Service Status
Rectifier Phase L2 Current Limit No No No H Service Status
Rectifier Phase L3 Current Limit
No No No H
Service Status
Rectifier Status Off No No No H User Status
Rectifier Status On No No No H User Status
Rectifier Switchgear Closed No No No No User Status
Rectifier Switchgear Open
No No No No
User Status
Rectifier Tripped No No No H
User Status
System Alarm Active No No
1
No User Status
System Notice Active No No No No User Status
UPS Normal No No No H User Status
*Log codes indicate where the UPS records the event: H = History log; HA = History and Active logs; and A = Active log only.
TTaabbllee 99.. CCoommmmaanndd
MMeessssaaggee
HHoorrnn PPhhoonnee
RReellaayy LLoogg**
IInnddiiccaattiioonn
Load Off Command Received Yes No No H Information Only
To Normal Mode Command
No No No H
Information Only
To Bypass Command No No No H Information Only
*Log codes indicate where the UPS records the event: H = History log; HA = History and Active logs; and A = Active log only.
Responding to System Events
For Internal Use Only