51 Eaton® 9390 (100–160 kVA) UPS Installation and Operation Manual 164201604—Rev F
88..22 UUssiinngg tthhee MMaaiinn MMeennuu
The UPS main menu bar allows you to display data in the information area to help you monitor and control UPS
operation. The following menus and options are available:
MMeennuu OOppttiioonn DDeessccrriippttiioonn
EVENTS Displays the list of Active System Events and a historical log of system events.
METERS Displays performance meters for the system or critical load.
CONTROLS Displays the System Controls screen.
SETUP Allows you to set the display contrast, set the date and time for the time stamp, configure the UPS serial
communication ports, and view the firmware version numbers.
LOAD OFF De-energizes the critical load and powers down the UPS.
CORD KIT INSTRUCTIONS
Eaton BladeUPS Cord Kit Instructions S 164201721 Rev 2 Draft 13-APR-2010
5
Removing the Existing Power Cords
To remove the existing power cords:
1. If the UPS and internal batteries are already installed, continue to
Step 2. If the UPS and internal batteries are not installed, continue
to Step 15.
2. You MUST shut down the UPS before replacing the cord assembly.
Continue to Step 3 to shut down a standalone UPS.
For parallel shutdown procedures, refer to the Eaton BladeUPS
(12 kVA) User's Guide and then continue to Step 11.
3. Switch the load connector circuit breaker to the OFF (O) position
(see Figure 2).
NOTE The load connector breaker controls the load connector only, not the output power.
4. Press any button on the front panel display to activate the menu
options. Select TURN UPS ON/OFF, TURN UPS OFF, and press the
button.
5. Confirm the selection. Press and hold the
button for three
seconds, until the UPS stops beeping.
The output relays open, the UPS transfers to Standby mode, and
the
indicator turns off.
6. Switch the UPS battery circuit breaker to the OFF (O) position.
7. If optional EBMs are installed, switch all EBM battery circuit
breakers to the OFF (O) position.
Disconnect the EBM cable from the UPS extended battery
connector.
8. Switch the UPS input circuit breaker to the OFF (O) position.
9. Switch off utility power where the UPS is connected.
10. Unplug the power cords.
Returns to Main Menu and Mimic screen from the Events, Meters, Controls, or Setup screens. Returns to the
main System Setup Level screen from a setup submenu.
88..22..11 MMiimmiicc SSccrreeeenn
Figure 19 shows the Main Menu and Mimic screen. To select the Mimic screen from the Events, Meters,
Controls, or Setup screens, press the
USING THE CONTROL PANEL
Eaton 9390 UPS (20–80 kVA) and 9390IT (20-40 kVA) Installation and Operation Manual S 164201603 Rev 4
8-3
8.2 Using the Main Menu
The UPS main menu bar allows you to display data in the information area to help you
monitor and control UPS operation. The following menus and options are available:
Menu Option Description
EVENTS Displays the list of Active System Events and a historical log of system events.
METERS Displays performance meters for the system or critical load.
CONTROLS Displays the System Controls screen.
SETUP Allows you to set the display contrast, set the date and time for the time stamp,
configure the UPS serial communication ports, and view the firmware version numbers.
LOAD OFF De-energizes the critical load and powers down the UPS.
Returns to Main Menu and Mimic screen from the Events, Meters, Controls, or Setup
screens. Returns to the main System Setup Level screen from a setup submenu.
8.2.1 Mimic Screen
Figure 8‐3 shows the Main Menu and Mimic screen. To select the Mimic screen from
the Events, Meters, Controls, or Setup screens, press the
pushbutton on the
current menu bar.
The Mimic screen shows the internal components of the UPS cabinet and a real‐time
graphical representation of the operating status of the system.
TIME: 11 : 35 : 43 DATE: 02 / 25 / 2004
CONTROLS LOAD OFF
METERSEVENTS SETUP
OUTPUT
BATT
UPS
INPUT
STSW
BYPASS
Figure 8‐3. Main Menu and Mimic Screen (Normal Mode)
pushbutton on the current menu bar.
The Mimic screen shows the internal components of the UPS cabinet and a real–time graphical representation
of the operating status of the system.
FFiigguurree 1199.. MMaaiinn MMeennuu aanndd MMiimmiicc SSccrreeeenn ((NNoorrmmaall MMooddee))
TIME: 11 : 35 : 43 DATE: 02 / 25 / 2004
CONTROLS LOAD OFF
METERS PUTESSTNEVE
OUTPUT
BATT
UPS
INPUT
STSW
BYPASS
Using the Control Panel