Page 17
614-09354-01_EN
ENGLISH
4. Insert the Normal AC source cable through the cable gland.
5. Connect the wires to the Normal AC source (Input) terminal blocks (do not remove the Input Bypass AC
jumper
4
and the UPS Input Bypass jumper inside the UPS I/O cover refer to the UPS User Manual)
6. Insert the Output cable through the cable gland.
7. Connect the wires to the Output terminal blocks.
8. Tighten the cable glands.
9. Slide back and secure the ModularEasy I/O cover
3
with the 2 screws.
10. Check EBM connected to UPS.
11. Connect the two UPS together with the 9PX parallel cable and lock it.
Use of specific parallel cable is mandatory for first start up and optimal use.
4. Power cables connection

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Eaton 9PX 5000i RT3U Netpack and is the answer not in the manual?

Eaton 9PX 5000i RT3U Netpack Specifications

General IconGeneral
Power Rating5000 VA / 4500 W
Rack Height3U
Output Frequency50/60 Hz
Output Power Factor0.9
TopologyDouble conversion online
Input Frequency40-70 Hz
Runtime at Half Load11 minutes
DisplayLCD
Form FactorRack/Tower
Output Voltage200/208/220/230/240V
Output ConnectionsIEC C13, IEC C19
Network ManagementYes, via Network Card
Battery TypeSealed Lead Acid
EfficiencyUp to 94%
CommunicationUSB, Serial, Relay
BatteriesInternal
Input Voltage Range176-276 VAC without derating (100-300 VAC with derating)