Maintenance and Alarms
Eaton ePDU G3 Operation Manual P-164000277—Rev 1 www.eaton.com/ePDU 140
2 211400 ePDU Input 1 Over Current Critical The specified section current amperage (A) reading is
greater than the value configured as the over current
critical alarm threshold.
2 212000 ePDU Input 1 Voltage No Threshold No section voltage threshold has been triggered.
2 212100 ePDU Input 1 Low Voltage Warning The specified section voltage reading is less than the
value configured as the low voltage warning
threshold.
2 212200 ePDU Input 1 Low Voltage Critical The specified section voltage reading is less than the
value configured as the low voltage critical threshold.
2 212300 ePDU Input 1 Over Voltage Warning The specified section voltage reading is greater than
the value configured as the over voltage warning
threshold.
2 212400 ePDU Input 1 Over Voltage Critical The specified section voltage reading is greater than
the value configured as the over voltage critical
threshold.
2 213000 ePDU Input 1 Frequency OK Utility frequency is within the +/- 3 Hz of Nominal
frequency.
2 213100 ePDU Input 1 Frequency Out of Range Utility frequency greater or less than +/- 3 Hz of
Nominal frequency.
2 214000 ePDU Input 2 Current No Threshold No section current threshold has been triggered.
2 214100 ePDU Input 2 Low Current Warning The current amperage (A) reading for the specified
section is less than the value configured as the low
current warning alarm threshold.
2 214200 ePDU Input 2 Low Current Critical The current amperage (A) reading for the specified
section is less than the value configured as the low
current critical alarm threshold.
2 214300 ePDU Input 2 High Current Warning The specified section current amperage (A) reading is
greater than the value configured as the over current
warning threshold.
2 214400 ePDU Input 2 High Current Critical The specified section current amperage (A) reading is
greater than the value configured as the over current
critical alarm threshold.
2 215000 ePDU Input 2 Voltage No Threshold No section voltage threshold has been triggered.
2 215100 ePDU Input 2 Low Voltage Warning The specified section voltage reading is less than the
value configured as the low voltage warning
threshold.
2 215200 ePDU Input 2 Low Voltage Critical The specified section voltage reading is less than the
value configured as the low voltage critical threshold.
2 215300 ePDU Input 2 High Voltage Warning The specified section voltage reading is greater than
the value configured as the over voltage warning
threshold.
2 215400 ePDU Input 2 High Voltage Critical The specified section voltage reading is greater than
the value configured as the over voltage critical
threshold.
2 216000 ePDU Input 2 Frequency OK The frequency is not out of range.
2 216100 ePDU Input 2 Frequency out of +/- 3 Hz
tolerance
The frequency is out of range.
Table 12. ePDU and User Alarms and Events (Continued)
Type Code
Identification and
Index Code Alarm or Event Description