Serial Interface Operation
Eaton ePDU G3 Operation Manual P-164000277—Rev 1 www.eaton.com/ePDU 72
XML Object Tables
This section includes tables that define ePDU CLI objects (Table 8) and System CLI Objects (Table 9 on
page 84).
Table 8. ePDU CLI Objects
XML Object Name Type Description Unit Access
Environment.ChangedStatus.CommunicationLost Timestamp Timestamp of last changing state of the alarm that has the
same name in the collection PresentStatus.
s RO
Environment.ChangedStatus.OverHumidity Timestamp Timestamp of last changing state of the alarm that has the
same name in the collection PresentStatus.
s RO
Environment.ChangedStatus.OverTemperature Timestamp Timestamp of last changing state of the alarm that has the
same name in the collection PresentStatus.
s RO
Environment.Humidity Measure Measured Humidity on environmental monitoring probe.
0 when no probe is connected or when the probe does not
have a humidity sensor.
d% RO
Environment.Input[1].ChangedStatus.Alarm Timestamp Timestamp of last changing state of the alarm that has the
same name in the collection PresentStatus.
s RO
Environment.Input[1].iName String[31] Contact 1 friendly name - RW
Environment.Input[1].PresentStatus.Alarm AlarmL1 Dry Contact alarm. Set according to the dry contact State
and the parameter State[0] or [1].Level
0: Alarm not active
1: Alarm active
Ex: State=0 AND State[0].Level=3 then Alarm=1
- RO
Environment.Input[1].PresentStatus.State Measure Dry Contact state
0: Open
1: Close
- RO
Environment.Input[1].State[0].Level Parameter Dry contact Config
1: Open makes just informational 0 into State.
2: Open makes Warning trap
3: Open makes Alarm trap
- RW
Environment.Input[1].State[1].Level Parameter Dry contact Config
1: Close makes just informational 0 into State.
2: Close makes Warning trap
3: Close makes Alarm trap
- RW
Environment.Input[2].ChangedStatus.Alarm Timestamp Timestamp of last changing state of the alarm that has the
same name in the collection PresentStatus.
s RO
Environment.Input[2].iName String[31] Contact 2 friendly name - RW
Environment.Input[2].PresentStatus.Alarm AlarmL1 Dry Contact alarm. Set according to the dry contact State
and the parameter State[0] or [1].Level
0: Alarm not active
1: Alarm active
Ex: State=0 AND State[0].Level=3 then Alarm=1
- RO
Environment.Input[2].PresentStatus.State Measure Dry Contact state
0: Open
1: Close
- RO